Effect of moisture and thermal degradation on the activation energy of oil-paper insulation in frequency domain spectroscopy measurement

被引:25
作者
Gao, Jun [1 ]
Yang, Lijun [1 ]
Wang, Youyuan [1 ]
Liu, Xiao [1 ]
Du, Yongyong [1 ]
Yao, Renyun [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
spectroscopy; transformer oil; moisture; reliability; statistical analysis; polymerisation; thermal degradation; activation energy; frequency domain spectroscopy measurement; transformer oil-paper insulation; FDS measurements; master curve technique; Arrhenius equation; moisture content; electron volt energy 1; 06; eV; electron volt energy 0; 88; model transformer; two-way ANOVA; moisture contents; oil-impregnated pressboards; DIELECTRIC RESPONSE; TRANSFORMER INSULATION; PARAMETERS; TEMPERATURE; DIAGNOSIS; POLARIZATION; TRANSIENT; IMPACT;
D O I
10.1049/iet-gtd.2015.0946
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency domain spectroscopy (FDS) is widely used to diagnose the condition of transformer oil-paper insulation. However, FDS measurements are highly temperature dependent. The master curve technique is the most common method to remove the temperature effect on FDS, but the reliability of this method is largely dependent on the value of the activation energy, which can be affected by moisture content and thermal degradation degree. To understand the effects of these two factors on the activation energy, FDS measurements at different temperatures were performed on oil-impregnated pressboards with different thermal degradation degrees and moisture contents. The activation energies of the pressboards were calculated using the Arrhenius equation. Results show that they vary between 0.88 and 1.06 eV along with thermal degradation degree and moisture. The two-way ANOVA indicates that the effects of these two factors on activation energy are not significant at 95% confidence level when the degree of polymerisation (DP) changes from 415 to 1300 and when the moisture does not exceed 4%. The average activation energy (0.95 eV) can be utilised to generalise the Arrhenius equation to better eliminate the temperature effects. Finally, FDS measurements on a model transformer are performed to verify the effectiveness of the proposed technique.
引用
收藏
页码:2042 / 2049
页数:8
相关论文
共 24 条
[1]   Influence of Temperature and Moisture Content on Frequency Response Analysis of Transformer Winding [J].
Bagheri, Mehdi ;
Phung, B. T. ;
Blackburn, Trevor .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) :1393-1404
[2]  
Der Houhanessian V., 1998, THESIS SWISS FED I T
[3]   Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation [J].
Ekanayake, Chandima ;
Gubanski, Stanislaw M. ;
Graczkowski, Andrzej ;
Walczak, Krzysztof .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1309-1317
[4]   Effect of Thermal Transient on the Polarization and Depolarization Current Measurements of Oil-Paper Insulation [J].
Fofana, I. ;
Hemmatjou, H. ;
Meghnefi, F. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (02) :513-520
[5]   On the Frequency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures [J].
Fofana, I. ;
Hemmatjou, H. ;
Meghnefi, F. ;
Farzaneh, M. ;
Setayeshmehr, A. ;
Borsi, H. ;
Gockenbach, E. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) :799-807
[6]   Moisture in Cellulose Insulation of Power Transformers - Statistics [J].
Gielniak, J. ;
Graczkowski, A. ;
Moranda, H. ;
Przybylek, P. ;
Walczak, K. ;
Nadolny, Z. ;
Moscicka-Grzesiak, H. ;
Feser, K. ;
Gubanski, S. M. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (03) :982-987
[7]  
Gielniak J, 2009, MATER SCI-POLAND, V27, P1199
[8]   On the Feasibility of Using Poles Computed from Frequency Domain Spectroscopy to Assess Oil Impregnated Paper Insulation Conditions [J].
Hadjadj, Yazid ;
Meghnefi, Fethi ;
Fofana, Issouf ;
Ezzaidi, Hassan .
ENERGIES, 2013, 6 (04) :2204-2220
[9]  
Jadav RB, 2014, IEEE T DIELECT EL IN, V21, P369, DOI [10.1109/TDEI.2013.003984, 10.1109/TDEI.2014.6740761]
[10]   Calculation of the Activation Energy of Oil-Paper Insulation in a Distribution Transformer [J].
Koufakis, Emmanuel I. ;
Halevidis, Constantinos D. ;
Polykrati, Aikaterini D. ;
Tsarabaris, Panagiotis T. .
IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (02) :52-58