Accurate prediction of damping in large interconnected power systems with the aid of regression analysis

被引:24
作者
Archer, Brian A. [1 ]
Annakkage, Udaya D. [2 ]
Jayasekara, Bathiya [3 ]
Wijetunge, Punya [4 ]
机构
[1] Manitoba Hydro, Winnipeg, MB R3C 2P4, Canada
[2] Univ Manitoba, Dept Elect & Comp Sci, Winnipeg, MB R3T 5V6, Canada
[3] TransGrid Solut Inc, Winnipeg, MB R3T 6B6, Canada
[4] Univ Manitoba, Dept Math, Winnipeg, MB R3T 2N2, Canada
关键词
damping; mode tracking; phasor measurement unit; regression analysis; wide area measurement;
D O I
10.1109/TPWRS.2008.926708
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces the use of regression analysis in the study of small signal stability in large interconnected power systems. Results demonstrate the usefulness of this approach in better understanding the nature of dominant electromechanical modes of oscillation. and in accurately predicting the damping on these modes. The usefulness of this approach in identifying strong correlations between system damping and distinct measurable and adjustable power system quantities such as generator output, line flows, bus voltages, and bus angles is presented. Results suggest that this approach may be useful in optimizing the location of traditional power system online recording devices, such as dynamic swing recorders (DSRs) as well as real-time monitoring devices such as phasor measurement units (PMUs). Sensitivity studies show that power system information obtained may be useful in providing an additional tool to help system operators optimize the dispatch of generating resources. It would also be useful in providing more realistic feedback from the power system and aid in the decision making regarding dynamic stability and its effect on appropriate system topology, loading levels, and allowable transfer levels in real time.
引用
收藏
页码:1170 / 1178
页数:9
相关论文
共 20 条
  • [1] ABRAHAM B, 2005, STAT METHODS FORCAST
  • [2] ANDERSON T, 1999, P IEEE POW ENG SOC S
  • [3] ARCHER BA, 2005, P IEEE POW ENG SOC G
  • [4] Archer BA, 2002, P IEEE CAN C EL COMP
  • [5] ARCHER BA, 2002, P IEEE POW ENG SOC W
  • [6] FERNANDO I, 2003, P INT C POW SYST TRA
  • [7] HAUER JF, 2005, ELECT POWER ENG HDB, pCH14
  • [8] HAUER JF, 2007, USE WECC WAMS STAGED
  • [9] Derivation of an accurate polynomial representation of the transient stability boundary
    Jayasekara, Bathiya
    Annakkage, Udaya D.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) : 1856 - 1863
  • [10] Kundur P., 1994, POWER SYSTEM STABILI