Analysis of zero-mode inrush current characteristics of converter transformers

被引:1
|
作者
Liu, Zhichang [1 ]
Yin, Xin [2 ]
Pan, Yuanlin [1 ]
Xi, Wei [3 ]
Yin, Xianggen [1 ]
Liu, Binyan [1 ]
机构
[1] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan, Hubei, Peoples R China
[2] Univ Liverpool, Liverpool L69 3GJ, Merseyside, England
[3] China Southern Power Grid Co Ltd, Digital Grid Res Inst, Guangzhou, Guangdong, Peoples R China
来源
2021 56TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC 2021): POWERING NET ZERO EMISSIONS | 2021年
关键词
converter transformer; inrush current; sympathetic interaction; zero-mode inrush current; PART I;
D O I
10.1109/UPEC50034.2021.9548277
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In recent years, there have been situations in which the zero-sequence protection of the transformer has been incorrectly operated due to the converter transformer energizing or fault recovery. For converter transformers, maloperation may also occur. However, there is almost no theoretical research on the zero-mode inrush currents of converter transformers. This paper studies the characteristics of the zero-mode inrush currents of the converter transformers, including the relationship between the amplitude and attenuation characteristics of the zero-mode inrush currents of converter transformers, and their relationship with the system resistance, remanence, and closing angle. First, based on the T-type equivalent circuit of the transformer, the equivalent circuit of the zero-mode inrush current of each transformer is obtained. On this basis, the amplitude relationship of the zero-mode inrush currents of different converter transformers is obtained: the zero-mode inrush current of the energizing pole YY transformer becomes larger than the YD transformer, the energized pole YD becomes greater than the YY transformer, and the YY transformer zero-mode inrush current rises from 0. It is also analyzed that the sympathetic interaction will make the attenuation of the converter transformer zero-mode inrush current slower. The system resistance mainly affects the initial attenuation speed, and the later attenuation speed is mainly determined by the converter transformer leakage reactance. Finally, PSCAD modeling and simulation are carried out to verify the accuracy of the theoretical analysis.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Mathematical Analysis for Zero-Mode Inrush Current of Transformer and Its Equivalent Circuit
    Wang Y.
    Cao W.
    Huang M.
    Yin X.
    Zeng G.
    Li Y.
    Liu W.
    Chen Q.
    Wang Z.
    Liu K.
    Cao, Wenbin (1019097704@qq.com), 2018, Power System Technology Press (42): : 3960 - 3968
  • [2] A new scheme of zero-sequence overcurrent protection of converter transformer based on zero-mode inrush current characteristics in station area
    Pan, Yuanlin
    Liu, Zhichang
    Yin, Xin
    Xi, Wei
    Yin, Xianggen
    Liu, Binyan
    ENERGY REPORTS, 2022, 8 : 1257 - 1263
  • [3] A new scheme of zero-sequence overcurrent protection of converter transformer based on zero-mode inrush current characteristics in station area
    Pan, Yuanlin
    Liu, Zhichang
    Yin, Xin
    Xi, Wei
    Yin, Xianggen
    Liu, Binyan
    Energy Reports, 2022, 8 : 1257 - 1263
  • [4] Characteristic analysis of zero-mode inrush current of high-impedance transformer
    Cao, Wenbin
    Yin, Xianggen
    Zhang, Zhe
    Pan, Yuanlin
    Wang, Yuxue
    Yin, Xiangyuan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 117
  • [5] Zero-Mode Inrush Current Characteristics and Zero-Sequence Protection Countermeasure Under Sympathetic Interaction
    Pan, Yuanlin
    Yin, Xianggen
    Yin, Xin
    Lai, Jinmu
    Xu, Cheng
    Han, Ke
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 3669 - 3678
  • [6] Study on zero-mode inrush current characteristics and its influence on protection under sympathetic interaction
    Pan, Yuanlin
    Yin, Xin
    Yin, Xianggen
    Zhang, Zhe
    Jiang, Lin
    Cao, Wenbin
    Liu, Binyan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 137
  • [7] Study on zero-mode inrush current characteristics and dynamic physical simulation tests of high-impedance transformer
    Yin X.
    Cao W.
    Pan Y.
    Wang M.
    Yin X.
    Wang Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2020, 48 (05): : 1 - 9
  • [8] A Simulation Study of the Influence of Magnetizing Inrush Current and Sympathetic Inrush Current of Converter Transformers
    Li, Rui
    Jiang, Han
    Huang, Biyue
    Sun, Haishun
    He, Chenying
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 2282 - 2286
  • [9] Characteristics of inrush current of present designs of power transformers
    Girgis, Ramsis S.
    teNyenhuis, Ed G.
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 4912 - +
  • [10] The Impact of Zero-Mode Inrush Current of T-Hin on Zero-Sequence Overcurrent Protection and an Improved Protection with the Second Harmonic Restraint
    Cao, Wenbin
    Yin, Xianggen
    Chen, Yongxin
    Pan, Yuanlin
    Yin, Xiangyuan
    Wang, Yuxue
    ENERGIES, 2019, 12 (15)