Performance numerical analysis on an internally-cooled liquid desiccant dehumidifier

被引:0
作者
Chan, X. M. [1 ]
Liu, X. H. [1 ]
Jiang, Y. [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci & Technol, Beijing 100084, Peoples R China
来源
BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS | 2007年
关键词
internally-cooled; dehumidifier; heat and mass transfer; simulation;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the internally-cooled liquid desiccant dehumidifier (ICLDD). cooling medium is introduced to carry away the vaporization latent heat, which enhances effectiveness of heat and mass transfer process between liquid desiccant and air. Numerical method is adopted in this paper to analyze the performance of ICLDD. Theoretical model of beat and mass transfer process is established and verified by available experimental results. The field-distributions and outlet parameters of three fluids (air, solution, water) in the dehumidifier are then emphatically analyzed to evaluate performance of the dehumidifier. The comparison between adiabatic dehumidifier and internally-cooled one is conducted, and it is found that the moisture removal rate in internally-cooled dehumidifier is 20% higher than the adiabatic one at the same operating condition.
引用
收藏
页码:607 / 613
页数:7
相关论文
共 8 条
[1]  
*AIL RES, 2006, SOA3000 PROD BROCH
[2]  
JIANG Y, 2004, NUANTONG KONGTIAO HV, V34, P88
[3]  
Khan AY, 1998, INT J ENERG RES, V22, P813, DOI 10.1002/(SICI)1099-114X(199807)22:9<813::AID-ER403>3.0.CO
[4]  
2-M
[5]   Cooling and dehumidification performance analysis of internally-cooled liquid desiccant absorbers [J].
Khan, AY .
APPLIED THERMAL ENGINEERING, 1998, 18 (05) :265-281
[6]   Modelling and parametric analysis of heat and mass transfer performance of a hybrid liquid desiccant absorber [J].
Khan, AY ;
Martinez, JL .
ENERGY CONVERSION AND MANAGEMENT, 1998, 39 (10) :1095-1112
[7]   Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator [J].
Liu, X. H. ;
Jiang, Y. ;
Qu, K. Y. .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (02) :546-554
[8]  
Lowenstein A., 2006, P ASME INT SOL EN C