Research on Overload Capability of Oil-immersed Distribution Transformer Based on Hot Spot Temperature Model

被引:0
作者
Wang, Haifei [1 ]
Xue, Manyu [1 ]
Wang, Tingkang [1 ]
Hou, Yuning [1 ]
Chen, Jianchun [1 ]
Sun, Jianming [2 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan, Peoples R China
[2] China Railway Fourth Survey & Design Inst Grp Co, Wuhan, Peoples R China
来源
2019 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2019) | 2019年
关键词
the oil-immersed distribution transformer; the allowable overload time; the allowable overload ratio; remaining service life;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As the user load continues to increase, the safety accidents caused by the overload of the transformer frequently occur. In order to improve the safety and stability of the transformer operation, this paper conducts an in-depth study on the overload capability of the transformer based on the hot spot temperature model. When the oil-immersed distribution transformer is overloaded, the internal temperature of the transformer rises, causing insulation aging and reducing the service life. This paper first introduces the characteristics of distribution transformers in different types of loads, and analyzes the changes occurring inside the transformers during overload operation, and then based on the hot water temperature calculation model in GB/T 1094. 7-2008 standard, from the perspective of operating temperature and heat aging, The research and analysis of the overload capacity of the distribution transformer is carried out, and the relationship between the allowable overload time of the transformer and the allowable overload multiple is obtained, and the theoretical analysis of the life loss is made.
引用
收藏
页码:4478 / 4482
页数:5
相关论文
empty
未找到相关数据