摘要
Metals constitute some of the major materials for making water delivery pipelines. However, the service life of metallic pipelines is affected by corrosion. Mild Steel (MS), Galvanized Steel (GS) and Copper were selected based on their strength and corrosion resistance. They were subjected to Potentiodynamic Polarization (PP) and Electrochemical Impedance Spectroscopy (EIS) investigations using water as the electrolyte from selected sampling points (A, B, C, D and E) on the University of Lagos, Akoka water distribution network. Corrosion current density (I-corr) and Impedance (Z) were measured in A/mm(2) and ohms respectively. The morphology of the corroded samples was examined using Scanning Electron Microscope (SEM). The result obtained from PP investigation showed I-corr in the low range for the three metals considered. Similarly, for EIS, Z values measured were high for MS, GS and Cu. Both methods indicated that Cu was the most corrosion resistant material, closely followed by GS and lastly MS. The SEM images clearly showed that among the three specimens, the morphology of Cu remained unaffected by the environment. On the other hand, MS and GS showed evidences of corrosion with pits. The large amounts of iron established in the studied water distribution system, confirmed corrosion of water pipes.
引用
收藏
页码:43 / 49
页数:7
相关论文
共 18 条
  • [1] Aina AT., 2016, International Journal Research Environment Study, V3, P93
  • [2] Changes in water quality in the Owabi water treatment plant in Ghana
    Akoto O.
    Gyamfi O.
    Darko G.
    Barnes V.R.
    [J]. Applied Water Science, 2017, 7 (1) : 175 - 186
  • [3] Inhibition of the pitting corrosion of 304 stainless steel in 0.5 M hydrochloric acid solution by heptamolybdate ions
    Albrimi, Y. Ait
    Addi, A. Ait
    Douch, J.
    Souto, R. M.
    Hamdani, M.
    [J]. CORROSION SCIENCE, 2015, 90 : 522 - 528
  • [4] Passivity of Sanicro28 (UNS N-08028) stainless steel in polluted phosphoric acid at different temperatures studied by electrochemical impedance spectroscopy and Mott-Schottky analysis
    BenSalah, M.
    Sabot, R.
    Triki, E.
    Dhouibi, L.
    Refait, Ph.
    Jeannin, M.
    [J]. CORROSION SCIENCE, 2014, 86 : 61 - 70
  • [5] Bhave P. R, 2011, ENV ENG, V104, P799
  • [6] Microbially influenced corrosion of galvanized steel pipes in aerobic water systems
    Bolton, N.
    Critchley, M.
    Fabien, R.
    Cromar, N.
    Fallowfield, H.
    [J]. JOURNAL OF APPLIED MICROBIOLOGY, 2010, 109 (01) : 239 - 247
  • [7] Toward a Slow-Release Borate Inhibitor To Control Mild Steel Corrosion in Simulated Recirculating Water
    Cui, Jun
    Yang, Yange
    Li, Xiuqing
    Yuan, Wenjiao
    Pei, Yuansheng
    [J]. ACS APPLIED MATERIALS & INTERFACES, 2018, 10 (04) : 4183 - 4197
  • [8] Corrosion behaviour and biocorrosion of galvanized steel water distribution systems
    Delaunois, F.
    Tosar, F.
    Vitry, V.
    [J]. BIOELECTROCHEMISTRY, 2014, 97 : 110 - 119
  • [9] Corrosion failure analysis of galvanized steel pipes in a water irrigation system
    Della Rovere, C. A.
    Silva, R.
    Moretti, C.
    Kuri, S. E.
    [J]. ENGINEERING FAILURE ANALYSIS, 2013, 33 : 381 - 386
  • [10] Gamry Instruments, 2018, TOT HARM DIST THEOR