Power Transformer Ferroresonance Suppression by Shunt Reactor Switching

被引:0
|
作者
Ang, S. P. [1 ]
Wang, Z. D. [1 ]
Jarman, P. [2 ]
Osborne, M. [2 ]
机构
[1] Univ Manchester, Manchester M13 9PL, Lancs, England
[2] Natl Grid, Warwick, England
关键词
ATP; Circuit breaker; Ferroresonance; Nonlinear inductance; Power Transformers; Shunt reactor; VOLTAGE TRANSFORMERS; CIRCUIT;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a case study, carried out on behalf of National Grid, regarding the likelihood for sustained fundamental frequency ferroresonance on a particular circuit configuration. The study considered a complex arrangement including a mesh corner substation connected by overhead line to a transformer feeder. The study investigated the effectiveness of mitigation to quench the intended ferroresonance by switching-in a 60 MVA shunt reactor which is connected at the 13 kV tertiary winding. The modeling work has been carried out using the generally available ATP software.
引用
收藏
页码:865 / +
页数:2
相关论文
共 50 条
  • [1] Effect of Shunt Capacitance on Ferroresonance Model for Distribution Voltage Transformer
    Malek, Zulkurnain Abdul
    Mirazimi, S. J.
    Mehranzamir, Kamyar
    Salimi, Behnam
    2012 IEEE SYMPOSIUM ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ISIEA 2012), 2012,
  • [2] Controlled Switching of Power Transformer and Shunt Reactors for Minimization of Switching Transients: A Review
    Kumar A.
    Perveen R.
    Parikh U.
    Journal of The Institution of Engineers (India): Series B, 2022, 103 (03) : 1013 - 1024
  • [3] Study of the Impact of Switching Transient Overvoltages on Ferroresonance of CCVT in Series and Shunt Compensated Power Systems
    Tajdinian, Mohsen
    Allahbakhshi, Mehdi
    Biswal, Sandeep
    Malik, Om P.
    Behi, Donya
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2020, 16 (08) : 5032 - 5041
  • [4] Analysis of Ferroresonance in a Power Transformer with Multiple Nonlinearities
    Kumar, Goutham
    Rajan, Saravanaselvan
    Rangarajan, Ramanujam
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2006, 7 (02): : 1 - 15
  • [5] Elimination of chaotic ferroresonance in power transformer by ISFCL
    Fordoei, H. R. Abbasi
    Heydari, H.
    Afsari, S. A.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 68 : 132 - 141
  • [6] Effect of Circuit Breaker Shunt Resistance on Chaotic Ferroresonance in Voltage Transformer
    Radmanesh, Hamid
    Rostami, Mehrdad
    ADVANCES IN ELECTRICAL AND COMPUTER ENGINEERING, 2010, 10 (03) : 71 - 77
  • [7] Analysis and Suppression of the Coupling Capacitor Voltage Transformer Ferroresonance Phenomenon
    Ajaei, Firouz Badrkhani
    Sanaye-Pasand, Majid
    Rezaei-Zare, Afshin
    Iravani, Reza
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 1968 - 1977
  • [8] Study of a shunt reactor with transformer function
    Egawa, T
    Kyono, M
    Misawa, K
    IEEE TRANSACTIONS ON MAGNETICS, 1997, 33 (02) : 1235 - 1238
  • [9] Study of a shunt reactor with transformer function
    Egawa, Takeshi
    Kyono, Mikio
    Misawa, Kazutaka
    IEEE Transactions on Magnetics, 1997, 33 (2 pt 2): : 1235 - 1238