Evaluation of a typical integrated solar absorption cooling system has been carried out to determine its overall performance. Analysis of the results revealed an operational efficiency of 61% for the solar collectors at a mean differential temperature (Delta T) of 51 degrees C as compared with the manufacturer's rating of 70% at a Delta T of 60 degrees C. The absorption chiller did however perform quite satisfactorily and achieved a coefficient of performance (COP) of 0.69 as compared with the manufacturer's rating of 0.7 despite the slight deviation at the collectors end. The installation strategy for the hot water storage tanks also appears to have achieved its objective of maintaining controlled temperature stratification in the tanks. It could therefore be concluded that the system has proved its potential as a viable cooling technology for application in buildings. However, in order to maintain appropriate hot water supply temperature during low solar radiation levels, supplementary heat source such as gas or biomass fired system would have to be considered and incorporated into solar absorption cooling systems. (c) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:395 / 402
页数:8
相关论文
共 21 条
[1]   Performance assessment of an integrated free cooling and solar powered single-effect lithium bromide-water absorption chiller [J].
Ali, Ahmed Hamza H. ;
Noeres, Peter ;
Pollerberg, Clemens .
SOLAR ENERGY, 2008, 82 (11) :1021-1030
[2]  
[Anonymous], 2011, Technology Roadmap Energy-efficient Buildings: Heating and Cooling Equipment
[3]  
[Anonymous], EN TECHN PERSP
[4]   Simulation and optimization of a LiBr solar absorption cooling system with evacuated tube collectors [J].
Assilzadeh, F ;
Kalogirou, SA ;
Ali, Y ;
Sopian, K .
RENEWABLE ENERGY, 2005, 30 (08) :1143-1159
[5]   Solar absorption cooling plant in Seville [J].
Bermejo, Pablo ;
Javier Pino, Francisco ;
Rosa, Felipe .
SOLAR ENERGY, 2010, 84 (08) :1503-1512
[6]  
Cullen JM, 2011, ENVIRON SCI TECHNOL, P1711
[7]   Urban energy use and carbon emissions from cities in China and policy implications [J].
Dhakal, Shobhakar .
ENERGY POLICY, 2009, 37 (11) :4208-4219
[8]  
Duffie J.A., 1991, Solar Engineering of Thermal Processes, Vsecond
[9]  
IEA. International energy Agency, 2002, TECHN REP TASK 25 SO
[10]  
Jiangsu Sunrain Solar Energy Co. Ltd, JIANGS SUNR SOL EN C