Experimental investigation of the hydraulic characteristics of a counter flow wet cooling tower

被引:29
作者
Lemouari, M. [1 ,3 ]
Boumaza, M. [2 ,3 ]
Kaabi, A. [3 ]
机构
[1] Univ Bejaia, Dept Proc Engn, Fac Technol, Bejaia 06000, Algeria
[2] King Saud Univ, Coll Engn, Dept Chem Engn, Riyadh 11421, Saudi Arabia
[3] Univ Constantine, Dept Climat Engn, Fac Engn Sci, Constantine, Algeria
关键词
Wet; Cooling tower; Packing; Hydraulic characteristic; Regimes; Energy; PERFORMANCE; OPTIMIZATION; SYSTEMS; DESIGN;
D O I
10.1016/j.energy.2011.08.045
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermal and nuclear electric power plants as well as several industrial processes invariably discharge considerable energy to their surrounding by heat transfer. Although water drawn from a nearby river or lake can be employed to carry away this energy, cooling towers offer an excellent alternative particularly in locations where sufficient cooling water cannot be easily obtained from natural sources or where concern for the environment imposes some limits on the temperature at which cooling water can be returned to the surrounding. This paper concerns an experimental investigation of the hydraulic characteristics of a counter flow wet cooling tower. The tower contains a "VGA." (Vertical Grid Apparatus) type packing which is 0.42 m high and consists of four (04) galvanised sheets having a zigzag form, between which are disposed three (03) metallic vertical grids in parallel with a cross sectional test area of 0.15 m x 0.148 m. The present investigation is focused mainly on the effect of the air and water flow rates on the hydraulic characteristics of the cooling tower, for different inlet water temperatures. The two hydrodynamic operating regimes which were observed during the air/water contact operation within the tower, namely the Pellicular Regime (PR) and the Bubble and Dispersion Regime (BDR) have enabled to distinguish two different states of pressure drop characteristics. The first regime is characterized by low pressure drop values, while in the second regime, the pressure drop values are relatively much higher than those observed in the first one. The dependence between the pressure drop characteristics and the combined heat and mass transport (air water) through the packing inside the cooling tower is also highlighted. The obtained results indicate that this type of tower possesses relatively good hydraulic characteristics. This leads to the saving of energy. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:5815 / 5823
页数:9
相关论文
共 33 条
[1]  
*ARMF LTD, 1993, INSTR MAN BAS WAT CO
[2]   Experimental investigation of the performance of a counter-flow, packed-bed mechanical cooling tower [J].
Bedekar, SV ;
Nithiarasu, P ;
Seetharamu, KN .
ENERGY, 1998, 23 (11) :943-947
[3]   A new approach to analysis and optimization of evaporative cooling system II: Applications [J].
Chen, Qun ;
Pan, Ning ;
Guo, Zeng-Yuan .
ENERGY, 2011, 36 (05) :2890-2898
[4]   A new approach to analysis and optimization of evaporative cooling system I: Theory [J].
Chen, Qun ;
Yang, Kangding ;
Wang, Moran ;
Pan, Ning ;
Guo, Zeng-Yuan .
ENERGY, 2010, 35 (06) :2448-2454
[5]   Integrated analysis of cooling water systems: Modeling and experimental validation [J].
Cortinovis, Giorgia F. ;
Ribeiro, Marcelo T. ;
Paiva, Jose L. ;
Song, Tah W. ;
Pinto, Jose M. .
APPLIED THERMAL ENGINEERING, 2009, 29 (14-15) :3124-3131
[6]  
ERGUN S, 1952, CHEM ENG PROG, V48, P89
[7]   The investigation of cooling tower packing in various arrangements [J].
Goshayshi, HR ;
Missenden, JF .
APPLIED THERMAL ENGINEERING, 2000, 20 (01) :69-80
[8]   Cooling tower - an energy conservation resource [J].
Goshayshi, HR ;
Missenden, JF ;
Tozer, R .
APPLIED THERMAL ENGINEERING, 1999, 19 (11) :1223-1235
[9]  
GOSHAYSHI HR, 1998, 3 INT C SITHOC MAR S
[10]  
GOSHAYSHI HR, 1998, INT C EXH HEAT EXCH