Faults locations in automated distribution system

被引:19
作者
Gohokar, VN [1 ]
Khedkar, MK [1 ]
机构
[1] Shri Sant Gajanan Maharaj Coll Engn, Power Syst Lab, Shegaon 444203, Maharashtra, India
关键词
distribution automation; symbolic method; phasor estimation; short circuit faults; open conductor fault;
D O I
10.1016/j.epsr.2005.01.003
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents new techniques for locating short circuit and open conductor faults on automated distribution system. This is a unique method where short circuit and open conductor faults are treated simultaneously. The proposed fault location scheme is capable of accurately identifying the zone in which fault occurs. Temporary faults are also detected which may not result in a blown fuse. Data is made available to the substation remote terminal unit from various automated distribution system equipments. Decision is taken based upon the magnitude of fundamental frequency component of voltage and current phasor. Testing of proposed fault location method has been demonstrated on the laboratory model for its practical use. Analogues simulation results are obtained using electromagnetic transients program (EMTP). (c) 2005 Published by Elsevier B.V..
引用
收藏
页码:51 / 55
页数:5
相关论文
共 10 条