Analysis of Coupling Effects on Overhead VSC-HVDC Transmission Lines From AC Lines With Shared Right of Way

被引:37
作者
Ding, Hui [1 ]
Zhang, Yi [1 ]
Gole, Aniruddha M. [1 ]
Woodford, Dennis A. [2 ]
Han, Min Xiao [3 ]
Xiao, Xiang Ning [3 ]
机构
[1] Univ Manitoba, Dept Elect & Comp Engn, Winnipeg, MB R3T 5V6, Canada
[2] Elect Corp, Winnipeg, MB R3T 5P4, Canada
[3] N China Elect Power Univ, Minist Educ, Key Lab Power Syst Protect & Dynam Secur Monitori, Beijing 102206, Peoples R China
基金
加拿大自然科学与工程研究理事会;
关键词
AC/DC interaction; coupling; electromagnetic induction; induced voltage; parallel ac/dc transmission line; transposition; CORE SATURATION INSTABILITY; BURIED PIPELINE VOLTAGES; MITIGATION; PREDICTION; PARALLEL; CURRENTS; MODEL;
D O I
10.1109/TPWRD.2010.2043373
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The coupling of fundamental frequency voltages and currents on voltage-source converter (VSC)-HVDC overhead transmission lines from neighboring ac lines is analyzed. The complementary modulation components at dc and second harmonic frequencies on the ac side of the converter resulting from the fundamental frequency coupling are analyzed. A mathematical model is developed for the VSC converter that accurately represents modulation effects to and from its ac and dc sides. This model is shown to be significantly different from that of a conventional line-commutated converter. This model is validated by using electromagnetic transients simulation. The model is then combined with an accurate frequency-domain model of the transmission lines and the converter ac-side equipment, and used to conduct parametric analysis of the coupling effects. As the induced 0-Hz (dc) modulation component on the ac side is of serious concern, parametric plots are presented showing its variation with factors, such as ac/dc separation distance, paralleled length, transposition and VSC operating point.
引用
收藏
页码:2976 / 2986
页数:11
相关论文
共 34 条
[1]   Portable earthing equipment - An advanced maintenance technique for 400kV double circuit transmission line under induced voltage condition [J].
Agrawal, LN .
2000 IEEE ESMO - 2000 IEEE 9TH INTERNATIONAL CONFERENCE ON TRANSMISSION & DISTRIBUTION CONSTRUCTION, OPERATION & LIVE-LINE MAINTENANCE PROCEEDINGS, 2000, :384-391
[2]   A general applicable model for AC predictive and mitigation techniques for pipeline networks influenced by HV power lines [J].
Bortels, L ;
Deconinck, J ;
Munteanu, C ;
Topa, V .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :210-217
[3]   Prediction of core saturation instability at an HVDC converter [J].
Burton, RS ;
Fuchshuber, CF ;
Woodford, DA ;
Gole, AM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1961-1969
[4]   HVDC converter transformer core saturation instability: A frequency domain analysis [J].
Chen, S ;
Wood, AR ;
Arrillaga, J .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (01) :75-81
[5]   ZERO SEQUENCE CURRENTS IN AC-LINES CAUSED BY TRANSIENTS IN ADJACENT DC-LINES [J].
CHOPRA, N ;
GOLE, AM ;
CHAND, J ;
HAYWOOD, RW .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1873-1879
[6]   Comparison of transient and power frequency-induced voltages on a pipeline parallel to an overhead transmission line [J].
Cotton, Ian ;
Kopsidas, Konstantinos ;
Zhang, Yang .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1706-1714
[7]   PREDICTION METHOD FOR BURIED PIPELINE VOLTAGES DUE TO 60-HZ AC INDUCTIVE COUPLING .2. FIELD-TEST VERIFICATION [J].
DABKOWSKI, J ;
TAFLOVE, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (03) :788-794
[8]   THE COMPLEX GROUND RETURN PLANE - A SIMPLIFIED MODEL FOR HOMOGENEOUS AND MULTILAYER EARTH RETURN [J].
DERI, A ;
TEVAN, G ;
SEMLYEN, A ;
CASTANHEIRA, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (08) :3686-3693
[9]  
Dommel H., 1986, EMTP REFERENCE MANUA
[10]  
FLOREA GA, 2006, P IEEE 11 INT C IEEE, P1