Transient Response Study on Transformer Windings Under Impulse Voltage Stresses

被引:0
|
作者
Masdi, Hendri [1 ]
Mariun, Norman [2 ]
机构
[1] Univ Putra Malaysia, Dept Elect & Elect Engn, Fac Engn, Serdang 43400, Selangor Darul, Malaysia
[2] Univ Putra Malaysia, Res Management Ctr, Serdang, Malaysia
来源
INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE | 2010年 / 5卷 / 03期
关键词
Transient Overvoltage; EMTDC/PSCAD; Transformer Model;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The study reported in this paper was aimed to investigate transient response of power transformer when lightning current pass through its winding. Analysis of distribution voltage at the winding taps was done, both by experimental and numerical simulation, by applying IEC-71 standard current surge (8/20 mu s impulse current and 1.2/50 mu s impulse voltage). Transformer's constants as: R, L, C were derived from the transformer construction, which consists of 9 winding layers at HV-side. The wave-shapes of the voltage across the winding sections were recorded. The response of the windings was then compared with results of a simulation using EMTDC/PSCAD. The simulation based on an RLC network model resulted in wave-shapes that are in good agreement to those of the experiment. Both results of the simulation and experiment show that the distribution of the impulse voltage across the windings is non linear, especially during the period of fraction of microseconds. Furthermore, results of the investigation show that a simple capacitance network model is sufficient for study of the impulse voltage distribution across transformer windings. Copyright (C) 2010 Praise Worthy Prize S.r.l. - All rights reserved.
引用
收藏
页码:1022 / 1026
页数:5
相关论文
共 50 条
  • [21] A STUDY OF THE TRANSIENT VIBRATION OF TRANSFORMER WINDINGS
    Hong, Kaixing
    Huang, Hai
    Pan, Jie
    PROCEEDINGS OF THE 23RD INTERNATIONAL CONGRESS ON SOUND AND VIBRATION: FROM ANCIENT TO MODERN ACOUSTICS, 2016,
  • [22] Analysis of Fast Transient Voltage Distributions in Transformer Windings under Different Insulation Conditions
    Florkowski, Marek
    Furgal, Jakub
    Pajak, Piotr
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (06) : 1991 - 1998
  • [23] SIMPLIFIED MODELS FOR SIMULATING TRANSFORMER WINDINGS SUBJECT TO IMPULSE VOLTAGE.
    D'Amore, M.
    Salerno, M.
    1979,
  • [24] The effects of axial displacement of transformer windings on impulse and transferred voltage distribution
    Rahimpour, E
    Hamidi, N
    ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (6-7) : 509 - 514
  • [25] Lightning impulse voltage distribution over voltage transformer windings-Simulation and measurement
    Trkulja, Bojan
    Drandic, Ana
    Milardic, Viktor
    Zupan, Tomislav
    Ziger, Igor
    Filipovic-Grcic, Dalibor
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 147 : 185 - 191
  • [26] Interturn insulation characteristics for transformer windings using three ester types under lightning impulse voltage
    Miyagi, Katsunori
    Hanaoka, Ryoichi
    Matsushita, Keiichiro
    Wakimoto, Kiyoshi
    2019 IEEE 20TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2019,
  • [27] Impulse Voltage Distribution and Frequency Response of Intershield Windings
    Bagheri, Mehdi
    Phung, B. T.
    Naderi, Mohammad Salay
    IEEE ELECTRICAL INSULATION MAGAZINE, 2016, 32 (05) : 32 - 40
  • [28] VOLTAGE STRESSES PRODUCED BY APERIODIC AND OSCILLATING SYSTEM OVERVOLTAGES IN TRANSFORMER WINDINGS
    MUSIL, RJ
    PREININGER, G
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01): : 3 - 3
  • [29] Transient Voltage Distribution Characteristics of Ultrahigh-Voltage Transformer Windings under Impulses with Different Front Time
    Ni, Heli
    Zhao, Yi
    Guo, Ning
    Fan, Xing
    Li, Xiaoang
    Long, Tianjun
    Zhang, Qiaogen
    2018 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE (IPMHVC), 2018, : 387 - 390
  • [30] MECHANICAL STRESSES IN TRANSFORMER WINDINGS
    不详
    NATURE, 1946, 158 (4002) : 65 - 65