Prony-based optimal bayes fault classification of overcurrent protection

被引:33
作者
Faiz, Jawad [1 ]
Lotfi-fard, Saeed [1 ]
Shahri, Saied Haidarian [1 ]
机构
[1] Univ Tehran, Sch Elect & Comp Engn, Tehran 1439957131, Iran
关键词
fault; optimal Bayes classifier; overcurrent relay; prony method; switching;
D O I
10.1109/TPWRD.2006.886794
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The development of deregulation and demand for high-quality electrical energy has lead to a new requirement in different fields of power systems. In the protection field, this means that high sensitivity and fast operation during the fault are required while maltripping of relay protection is not acceptable. One case that may lead to a maltrip of the high-sensitive overcurrent relay is the starting current of the induction motor or inrush current of the transformer. This transient current has the potential to affect the correct operation of protection relays close to the component being switched. In the case of switching events, such transients must not lead to overcurrent relay operation; therefore, a reliable and secure relay response becomes a critical matter. Meanwhile, proper techniques must be used to prevent maltripping of such relays, due to transient currents in the network. In this paper, the optimal Bayes classifier is utilized to develop a method for discriminating the fault from nonfault events. The proposed method has been designed based on extracting the modal parameters of the current waveform using the Prony method. By feeding the fundamental frequency damping and ratio of the 2nd harmonic amplitude over the fundamental harmonic amplitude to the classifier, the fault case is discriminated from the switching case. The suitable performance of this algorithm is demonstrated by simulation of different faults and switching conditions on a power system using PSCAD/EMTDC software.
引用
收藏
页码:1326 / 1334
页数:9
相关论文
共 24 条
[1]   Elimination of transformer inrush currents by controlled switching - Part II: Application and performance considerations [J].
Brunke, JH ;
Frohlich, KJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (02) :281-285
[2]   PRONYS METHOD - AN EFFICIENT TOOL FOR THE ANALYSIS OF EARTH FAULT CURRENTS IN PETERSEN-COIL-PROTECTED NETWORKS [J].
CHAARI, O ;
BASTARD, P ;
MEUNIER, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) :1234-1241
[3]  
Dag O, 2004, 2004 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - POWERCON, VOLS 1 AND 2, P1309
[4]   A novel digital directional transformer protection technique based on wavelet packet [J].
Eissa, MM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :1830-1836
[5]   EFFECT OF WAVE-FORM DISTORTION ON PROTECTIVE RELAYS [J].
ELMORE, WA ;
KRAMER, CA ;
ZOCHOLL, SE .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (02) :404-411
[6]   A novel wavelet-based algorithm for discrimination of internal faults from magnetizing inrush currents in power transformers [J].
Faiz, Jawad ;
Lotfi-Fard, S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) :1989-1996
[7]  
Fukunaga K., 1990, INTRO STAT PATTERN R
[8]  
Gomez JC, 2001, IEEE IND APPLIC SOC, P1196, DOI 10.1109/IAS.2001.955648
[9]   A current-based solution for transformer differential protection -: Part I:: Problem statement [J].
Guzmán, A ;
Zocholl, S ;
Benmouyal, G ;
Altuve, HJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :485-491
[10]  
LOBOS T, 2001, P IEEE PROT POW TECH