Performance enhancement of ejector-absorption cooling cycle by re-arrangement of solution streamlines and adding RHE

被引:27
作者
Abed, Azher M. [1 ,2 ]
Alghoul, M. A. [1 ]
Sirawn, R. [1 ]
Al-Shamani, Ali Najah [1 ]
Sopian, K. [1 ]
机构
[1] Univ Kebangsaan Malaysia, SERI, Bangi 43600, Selangor, Malaysia
[2] Al Mustaqbal Univ Coll, Dept Air Conditioning & Refrigerat, Babylon, Iraq
关键词
Ejector-flash tank-absorption cooling cycle; NH3/H2O; Re-arrangement of solution streamlines; Adding RHE; Energy balance analysis; COP enhancement; FLASH-TANK; REFRIGERATION; OPTIMIZATION; SYSTEM;
D O I
10.1016/j.applthermaleng.2014.12.003
中图分类号
O414.1 [热力学];
学科分类号
摘要
Performance of ejector-flash tank-absorption cooling system working with NH3/H2O is still subject for further enhancement. The aim of this study is to optimize the utilization of the internal heat recovery of the system. Two modifications are considered, namely, a new arrangement of solution streamlines between the absorber and generator and adding a refrigerant heat exchanger (RHE) between the condenser and evaporator. Energy balance analysis is performed to compare the COP enhancement of the proposed cycle before and after modification. The COP of the proposed cycle after modification showed a significant COP enhancement about 12.2%. The COP increment with the new arrangement of the solution streamlines and adding RHE are 8% and 4.2% respectively. The results show that the cooling capacity increment of the proposed cycle with added RHE is 4.85%. Moreover, the results showed that the proposed cycle significantly reduced the generator thermal load and increased slightly the evaporator thermal load (i.e., cooling effect) compare to the cycle before modification. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:65 / 75
页数:11
相关论文
共 44 条
[1]   Review on solar-driven ejector refrigeration technologies [J].
Abdulateef, J. M. ;
Sopian, K. ;
Alghoul, M. A. ;
Sulaiman, M. Y. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (6-7) :1338-1349
[2]   OPTIMIZATION STUDY OF THE COMPRESSION ABSORPTION CYCLE [J].
AHLBY, L ;
HODGETT, D ;
BERNTSSON, T .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1991, 14 (01) :16-23
[3]  
[Anonymous], 1997, ASHRAE HDB
[4]  
[Anonymous], 2009, ASHRAE HDB
[5]  
Aphornratana S, 1998, INT J ENERG RES, V22, P195, DOI 10.1002/(SICI)1099-114X(19980310)22:3<195::AID-ER346>3.3.CO
[6]  
2-1
[7]  
Bourseau P., 1986, INT J R EFRIGERATION, V9, P206, DOI [10.1016/0140-7007(86)90092-7, DOI 10.1016/0140-7007(86)90092-7]
[8]   Recent developments in ejector refrigeration technologies [J].
Chen, Xiangjie ;
Omer, Siddig ;
Worall, Mark ;
Riffat, Saffa .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 19 :629-651
[9]   Performance evaluation of a two-stage CO2 cycle with gas injection in the cooling mode operation [J].
Cho, Honghyun ;
Baek, Changhyun ;
Park, Chasik ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (01) :40-46
[10]   Ejectors: applications in refrigeration technology [J].
Chunnanond, K ;
Aphornratana, S .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2004, 8 (02) :129-155