Operational characteristics in the three-phase transformer-type SFCL with neutral line based on sequential reclosing process

被引:5
作者
Cho, Y. S. [1 ]
Choi, H. S. [1 ]
Jung, B. I. [1 ]
机构
[1] Chosun Univ, Dept Elect Eng, Kwangju 501759, South Korea
来源
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS | 2011年 / 471卷 / 21-22期
关键词
Three-phase transformer-type SFCL; Neutral line; Reclosing operation duty; Recovery behavior; FAULT CURRENT LIMITER;
D O I
10.1016/j.physc.2011.05.191
中图分类号
O59 [应用物理学];
学科分类号
摘要
In a transformer-type superconducting fault current limiter (SFCL) with a neutral line, which is connected between the superconducting elements and secondary windings, we verified that the SFCL has excellent characteristics that induce the perfect simultaneous quench of the superconducting elements in the previous study. The application of the SFCL to the power networks requires its coordination with the reclosing operation duty, which protects a circuit. In this study, the fault current limiting and recovery characteristics of superconducting elements in the three-phase transformer-type SFCL with the neutral line were analyzed. The limiting rate of the fault current in the transformer-type SFCL could increased by an iron core, which allows quenching of the superconducting elements in a sound phase as well as in a faulted phase. In addition, the simultaneous quench led to uniform burdens on superconducting elements, all of which recovered their superconducting state within an opening cycle of a circuit breaker. Thus, the transformer-type SFCL with the neutral line could reliably conduct the fault current limiting and recovery operations of superconducting elements according to the reclosing operation duty and fault types. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1341 / 1347
页数:7
相关论文
共 8 条
[1]   Improvement on the power capacity of the transformer-type SFCL with neutral lines between secondary windings [J].
Cho, Y. S. ;
Choi, H. S. .
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2009, 469 (15-20) :1749-1753
[2]   Critical current equalization via neutral lines in a transformer-type SFCL [J].
Choi, Hyo-Sang ;
Cho, Yong-Sun .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) :733-736
[3]  
Fushiki K, 2007, IEEE T APPL SUPERCON, V17, P1815, DOI [10.1109/TASC.2007.898018, 10.1109/tasc.2007.898018]
[4]   Method of Recloser-Fuse Coordination in a Power Distribution System With Superconducting Fault Current Limiter [J].
Kim, M. H. ;
Lim, S. H. ;
Moon, J. F. ;
Kim, J. C. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1164-1167
[5]   Test Requirements and Performance Evaluation for Both Resistive and Inductive Superconducting Fault Current Limiters for 22.9 kV Electric Distribution Network in Korea [J].
Lee, B. W. ;
Rhee, S. B. .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1114-1117
[6]   Development of 6.6 kV/600 A superconducting fault current limiter using coated conductors [J].
Yazawa, T. ;
Koyanagi, K. ;
Takahashi, M. ;
Toba, K. ;
Takigami, H. ;
Urata, M. ;
Iijima, Y. ;
Saitoh, T. ;
Amemiya, N. ;
Shiohara, Y. ;
Ito, T. .
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2009, 469 (15-20) :1740-1744
[7]   Construction of testing facilities and verifying tests of a 22.9 kV/630 A class superconducting fault current limiter [J].
Yim, S. -W. ;
Yu, S. -D. ;
Kim, H. -R. ;
Kim, M. -J. ;
Park, C. -R. ;
Yang, S. -E. ;
Kim, W. -S. ;
Hyun, O-B. ;
Sim, J. ;
Park, K. -B. ;
Oh, I-S. .
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2010, 470 (20) :1611-1614
[8]   Study on Protection Coordination Between Protective Devices in a Power Distribution System With an SFCL [J].
You, Il-Kyoung ;
Lim, Sung-Hun ;
Kim, Jae-Chul ;
Hyun, Ok-Bae .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2010, 20 (03) :1168-1171