Preliminary real-scale experimental studies on cable fires in plenum

被引:3
作者
Fei, Y [1 ]
Zhou, JJ
Zou, YH
Li, PD
Lin, JZ
Chow, TT
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Anhua 230026, Peoples R China
[2] City Univ Hong Kong, Div Bldg Sci & Technol, Hong Kong, Hong Kong, Peoples R China
关键词
cable fire; plenum; real-scale flatlet model; fire performance; fire hazard;
D O I
10.1177/0734904103036285
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Series fire tests simulating cable fires in plenum caused by exposed and aged combustible cables were carried out in a real-scale flatlet model containing burn room, ceiling plenum, and target room. A special communication cable type insulated with HDPE and sheathed with LLDPE was utilized. A related fire reference scenario was designed to simulate how cables in plenum were involved in a fire from potential fire loads to substantial fuel by the role of an external flaming source and to characterize related fire issues. Major concerns are that how various amounts, various ignition means and different ventilation rates impact on fire performances (heat release rate, smoke temperature, smoke obscuration, combustion products, and toxicity) of cables in plenum. It is found that influences of these parameters are obvious. The burning of exposed tested cables in plenum easily poses a high potential of fire hazard even at a relatively low fire load.
引用
收藏
页码:465 / 484
页数:20
相关论文
共 27 条
[1]   Fire initiation and spread in overloaded communication system cable trays [J].
Alvares, N ;
Fernandez-Pello, AC .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2000, 21 (1-3) :51-57
[2]  
*ASHRAE, REQ FOR PROP ASHRAE
[3]  
Barnes MA., 1996, FIRE MATER, V20, P17, DOI [10.1002/(SICI)1099-1018(199601)20:1andlt
[4]  
17::AID-FAM554andgt
[5]  
3.0.CO
[6]  
2-C, DOI 10.1002/(SICI)1099-1018(199601)20:13.0.CO
[7]  
2-C]
[8]  
Barnes MA., 1996, FIRE MATER, V20, P1, DOI 10.1002/(SICI)1099-1018(199601)20:13.0.CO
[9]  
2-W
[10]  
BUKOWSKI RW, 1985, FIRE TECHNOL, V21, P252