A novel solar-assisted ground-source heat pump (SAGSHP) with seasonal heat-storage and heat cascade utilization: Field test and performance analysis

被引:28
作者
Sun, Tingting [1 ]
Yang, Lingyan [2 ]
Jin, Lu [1 ]
Luo, Zhiwen [3 ]
Zhang, Yan [4 ]
Liu, Yanzhu [5 ]
Wang, Zhengru [4 ]
机构
[1] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian 710000, Peoples R China
[2] China Acad Bldg Res, Beijing 100013, Peoples R China
[3] Univ Reading, Sch Construct Management & Engn, Reading RG6 6AY, Berks, England
[4] Haomaichangan Green Energy Ltd Shandong, Weifang 261000, Peoples R China
[5] Jian Engn Project Management Ltd Shandong, Zibo 255000, Peoples R China
基金
中国国家自然科学基金;
关键词
Solar-assisted ground-source heat pump; Seasonal heat-storage; Heat cascade utilization; Hybrid thermal system; Field testing; THERMAL-ENERGY STORAGE; COLD CLIMATE; SYSTEM; SIMULATION; MODEL; OPTIMIZATION; GSHP;
D O I
10.1016/j.solener.2020.03.030
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To maintain the energy quality with high temperature and reduce the energy loss of seasonal heat-storage in solar-assisted ground-source heat pumps (SAGSHPs), a novel SAGSHP system with the heat-cascading of borehole heat-exchangers was designed and its field-test was conducted in this paper. The borehole heat-exchangers were divided into two regions: the core region and the peripheral region. The core region can maintain a high temperature (e.g. 45 degrees C), which is much higher than in previous studies, and the heat from this region can be used directly, without the operation of a heat pump. A field-test was conducted in a community in the province Shandong, China. The results indicate that a sufficient soil-temperature gradient (the temperature is high in the core but low at the periphery) can be created and maintained. The monthly averaged borehole-wall-temperature difference between the borehole heat-exchangers (BHEs) at the core and the periphery can be as high as 30.1 degrees C. This means that both cascaded heat-storage and heat-utilization can be realized. In addition, an average performance of CCOP = 5.15 and SCOP = 4.66 can be achieved. Compared with previous studies, despite the lower CCOP, a higher SCOP can be attained, thanks to heat cascade storage and -utilization. The novel approach described in this paper represents a viable alternative for space heating in North China.
引用
收藏
页码:362 / 372
页数:11
相关论文
共 41 条
[1]  
Bai C., 2020, ENERGY BUILT ENV, V1, P1, DOI [10.1016/j.enbenv.2019.08.004, DOI 10.1016/J.ENBENV.2019.08.004]
[2]   German central solar heating plants with seasonal heat storage [J].
Bauer, D. ;
Marx, R. ;
Nussbicker-Lux, J. ;
Ochs, F. ;
Heidemann, W. ;
Mueller-Steinhagen, H. .
SOLAR ENERGY, 2010, 84 (04) :612-623
[3]   Solar and ground source heat-pump system [J].
Bi, YH ;
Guo, TW ;
Zhang, L ;
Chen, LG .
APPLIED ENERGY, 2004, 78 (02) :231-245
[4]   Performance analysis of a proposed solar assisted ground coupled heat pump system [J].
Chen, Xi ;
Yang, Hongxing .
APPLIED ENERGY, 2012, 97 :888-896
[5]   Long term operation of a solar assisted ground coupled heat pump system for space heating and domestic hot water [J].
Chen Xi ;
Lu Lin ;
Yang Hongxing .
ENERGY AND BUILDINGS, 2011, 43 (08) :1835-1844
[6]  
Chiasson A.D., 2003, ASHRAE T, V109, P487
[7]   A simulation model for solar assisted shallow ground heat exchangers in series arrangement [J].
Cimmino, Massimo ;
Eslami-Nejad, Parham .
ENERGY AND BUILDINGS, 2017, 157 :227-246
[8]   Experimental performance analysis of a solar assisted ground source heat pump system under different heating operation modes [J].
Dai, Lanhua ;
Li, Sufen ;
Lin DuanMu ;
Li, Xiangli ;
Shang, Yan ;
Dong, Ming .
APPLIED THERMAL ENGINEERING, 2015, 75 :325-333
[9]   An analysis of solar assisted ground source heat pumps in cold climates [J].
Emmi, Giuseppe ;
Zarrella, Angelo ;
De Carli, Michele ;
Galgaro, Antonio .
ENERGY CONVERSION AND MANAGEMENT, 2015, 106 :660-675
[10]   A simplified ground thermal response model for analyzing solar-assisted ground source heat pump systems [J].
Fine, Jamie P. ;
Nguyen, Hiep V. ;
Friedman, Jacob ;
Leong, Wey H. ;
Dworkin, Seth B. .
ENERGY CONVERSION AND MANAGEMENT, 2018, 165 :276-290