Method, algorithm and device for estimation of components above the harmonic frequency range up to 9 kHz

被引:9
|
作者
Tarasiuk, Tomasz [1 ]
机构
[1] Gdynia Maritime Univ, Dept Ship Elect Power Engn, PL-81225 Gdynia, Poland
关键词
Power quality; Fourier transform; Wavelet transform; IEC standards; Digital signal processor; WAVELET TRANSFORM; FOURIER; SYSTEMS;
D O I
10.1016/j.measurement.2010.09.046
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The paper presents a method of estimation of frequency groups with 200 Hz bandwidth in the frequency range from the 50th harmonic up to 9 kHz. The method consists of the application of a fast Fourier transform (FFT) for wavelet coefficients after input signal decomposition and partial synthesis for chosen frequency bands. It enables the computational complexity of the algorithm to be reduced and also attenuates influence of the fundamental component and low-frequency harmonics, as required by IEC Standard 61000-4-7. The particulars of this method are shown and analysis for a chosen wavelet family is provided. Further, the algorithm and its implementation in real device for power quality monitoring is presented. Finally, the results of measurements of two testing signals are shown. The required attenuation of fundamental component and required accuracy was obtained. (C) 2010 Published by Elsevier Ltd.
引用
收藏
页码:219 / 229
页数:11
相关论文
共 20 条
  • [1] A fast and accurate frequency estimation algorithm for sinusoidal signal with harmonic components
    Hu, Jinghua
    Pan, Mengchun
    Zeng, Zhidun
    Hu, Jiafei
    Chen, Dixiang
    Tian, Wugang
    Zhao, Jianqiang
    Du, Qingfa
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2016, 87 (10):
  • [2] Grid-tied Inverters in Renewable Energy Systems: Harmonic Emission in 2 to 9 kHz Frequency Range
    Rathnayake, Hansika
    Solatialkaran, Davood
    Zare, Firuz
    Sharma, Rahul
    2019 21ST EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE '19 ECCE EUROPE), 2019,
  • [3] Limits for voltage distortion in the frequency range 2 to 9 kHz
    Bollen, Math H. J.
    Ribeiro, Paulo F.
    Larsson, E. O. Anders
    Lundmark, C. Martin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) : 1481 - 1487
  • [4] A New High Frequency Grid Impedance Estimation Technique for the Frequency Range of 2 to 150 kHz
    AlyanNezhadi, M. M.
    Hassanpour, H.
    Zare, F.
    INTERNATIONAL JOURNAL OF ENGINEERING, 2018, 31 (10): : 1666 - 1674
  • [5] Harmonic Emissions in 0-9 kHz Frequency Range and Transient Effects in Grid-Connected Inverters Utilised in Solar Farms
    Yaghoobi, Jalil
    Zare, Firuz
    Solatialkaran, Davood
    2020 19TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2020,
  • [6] Equipment Currents in the Frequency Range 9-95 kHz, Measured in a Realistic Environment
    Roennberg, S. K.
    Wahlberg, M.
    Bollen, M. H. J.
    Lundmark, C. M.
    2008 13TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, VOLS 1 AND 2, 2008, : 26 - +
  • [7] Frequency Shifting and Filtering Algorithm for Power System Harmonic Estimation
    Shuai, Zhikang
    Zhang, Junhao
    Tang, Lu
    Teng, Zhaosheng
    Wen, He
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2019, 15 (03) : 1554 - 1565
  • [8] Harmonic Analysis of Grid-tied Active Front End Inverters for the Frequency Range of 0-9 kHz in Distribution Networks:Addressing Future Regulations
    Rathnayake, Hansika
    Khajeh, Kiarash Gharani
    Zare, Firuz
    Sharma, Rahul
    2019 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT), 2019, : 446 - 451
  • [9] Selected Aspects of Evaluation of Complete Frequency Spectra up to 9kHz according to Valid International Standard
    Bilik, Petr
    11TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2010, PROCEEDINGS, 2010, : 489 - 492
  • [10] Sampling Primary Power Standard from DC up to 9 kHz Using Commercial Off-The-Shelf Components
    Mester, Christian
    ENERGIES, 2021, 14 (08)