On-line PD monitoring system for rotating machines using narrow band detection of EM wave in GHz range

被引:0
作者
Muto, Hirotaka [1 ]
Kaneda, Yoshiharu [1 ]
Aoki, Hirohide [1 ]
Hamamoto, Osamu [2 ]
机构
[1] Mitsubishi Electr Corp, 8-1-1 Tsukaguchi Honmachi, Amagasaki, Hyogo 6618661, Japan
[2] Toshiba Mitsubishi Elect Ind Syst Corp, Maruoka, Fukui 8528004, Japan
来源
PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS | 2007年
关键词
coils; diagnosis; generators; insulation; micro strip antennas; motors; partial discharges;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
On-line PD monitoring system with higher sensitivity and low noise features was developed for rotating machines such as turbine generator and high voltage motor. By using narrow band detection in GHz region, the features were achieved. The system is composed of an antenna, a specifically designed signal processing circuit and data acquisition equipment. The antenna is so-called patch antenna and its dimension is approximately 120x120mm and is designed for detecting a specific narrow band frequency in GHz range. This type of antenna is very easy to install because the thin plate structure does not interfere other high voltage parts inside the rotating machine if installed on the inner wall of the machine housing. The antenna is connected to the amplifier adjusted for the frequency band of the antenna resulting in superior noise suppression. The sensitivity of the system was measured and confirmed to have a good linear correlation with conventional off-tine Qmax value from several hundreds pico Coulomb. This sensitivity is enough for on-line insulation monitoring for rotating machines because the low level PD activity during operation does not infer abnormality of the machines.
引用
收藏
页码:1093 / +
页数:2
相关论文
共 3 条
[1]   New noise rejection techniques on pulse-by-pulse basis for on-line partial discharge measurement of turbine generators - Response [J].
Itoh, K ;
Kaneda, Y ;
Kitamura, S ;
Kimura, K ;
Nishimura, A ;
Tanaka, T ;
Tokura, H ;
Okada, I .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1996, 11 (03) :593-594
[2]   Development of partial discharge monitor for turbine generators [J].
Itoh, K ;
Tsurimoto, T ;
Kaneda, Y ;
Kitamura, S ;
Kuroki, S ;
Ohsawa, T ;
Tanaka, H .
1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, :79-82
[3]  
KIMURA K, 2000, P CIGRE 2000, P11