Personal CO2 bubble: Context-dependent variations and wearable sensors usability

被引:30
作者
Ghahramani, Ali [1 ]
Pantelic, Jovan [1 ]
Vannucci, Matthew [1 ]
Pistore, Lorenza [1 ,2 ]
Liu, Shichao [1 ,3 ]
Gilligan, Brian [4 ]
Alyasin, Soheila [5 ]
Arens, Edward [1 ]
Kampshire, Kevin [4 ]
Sternberg, Esther [6 ]
机构
[1] Univ Calif Berkeley, Ctr Built Environm, Berkeley, CA 94720 USA
[2] Free Univ Bozen Bolzano, Fac Sci & Technol, Bolzano, Italy
[3] Worcester Polytech Inst, Dept Civil & Environm Engn, Worcester, MA 01609 USA
[4] Gen Serv Adm, Washington, DC USA
[5] Shiraz Univ Med Sci, Dept Pediat, Allergy Res Ctr, Shiraz, Iran
[6] Univ Arizona, Inst Pl Well Being & Performance, Tucson, AZ 85721 USA
关键词
CO2; exposure; Personal indoor air quality; Inhalation zone CO2 concentration; Occupant behavior; Wearable CO2 sensor; Ubiquitous sensing; AIR SUPPLY RATE; THERMAL COMFORT; CARBON-DIOXIDE; EXPOSURE; TEMPERATURE; VENTILATION; OPTIMIZATION; PERFORMANCE; POLLUTANTS; TRANSPORT;
D O I
10.1016/j.jobe.2018.11.015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
High CO2 concentration in inhaled air has been shown to negatively impact work performance and increase acute health symptoms. As respiratory CO2 is constantly exhaled, it may not dissipate in surrounding air in absence of adequate air movement and is instead re-inhaled into the airways (breathing in a CO2-rich bubble). In this study, we explored the impacts of context-dependent factors such as office activities, desk settings, and personal differences on the inhalation zone CO2 concentration and on concentrations at a below-neck wearable sensor. We found that all factors significantly impact measurements at both measuring points of our test subjects. Presence of a small portable desk fan was also found to significantly reduce the CO2 concentration. On average, we observed a 177 ppm reduction in CO2 concentration when using a fan, which is 25 ppm higher than the background CO2 measurement (650 ppm). Among 41 test subjects, we found distinct relationships between the inhalation zone CO2 concentration and the wearable sensor measurements and, by applying a hierarchical clustering algorithm, we found 4 clusters of relationships. While below-neck wearable sensors could be used as an exact measure of inhalation of CO2 concentration for 29% of the subjects, we identified a boundary point (917 ppm) separating high and low inhalation zone CO2 concentration measurements.
引用
收藏
页码:295 / 304
页数:10
相关论文
共 39 条
[1]   Real-time activity recognition for energy efficiency in buildings [J].
Ahmadi-Karvigh, Simin ;
Ghahramani, Ali ;
Becerik-Gerber, Burcin ;
Soibelman, Lucio .
APPLIED ENERGY, 2018, 211 :146-160
[2]   One size does not fit all: Understanding user preferences for building automation systems [J].
Ahmadi-Karvigh, Simin ;
Ghahramani, Ali ;
Becerik-Gerber, Burcin ;
Soibelman, Lucio .
ENERGY AND BUILDINGS, 2017, 145 :163-173
[3]   Associations of Cognitive Function Scores with Carbon Dioxide, Ventilation, and Volatile Organic Compound Exposures in Office Workers: A Controlled Exposure Study of Green and Conventional Office Environments [J].
Allen, Joseph G. ;
MacNaughton, Piers ;
Satish, Usha ;
Santanam, Suresh ;
Vallarino, Jose ;
Spengler, John D. .
ENVIRONMENTAL HEALTH PERSPECTIVES, 2016, 124 (06) :805-812
[4]  
ASHRAE Standard, 2010, P AM SOC HEAT REFR A
[5]   Use of a fan during sleep and the risk of sudden infant death syndrome [J].
Coleman-Phox, Kimberly ;
Odouli, Roxana ;
Li, De-Kun .
ARCHIVES OF PEDIATRICS & ADOLESCENT MEDICINE, 2008, 162 (10) :963-968
[6]   Personal reactive clouds: Introducing the concept of near-head chemistry [J].
Corsi, R. L. ;
Siegel, J. ;
Karamalegos, A. ;
Simon, H. ;
Morrison, G. C. .
ATMOSPHERIC ENVIRONMENT, 2007, 41 (15) :3161-3165
[7]  
Erdman C.A., 2002, P IND AIR 2002 C MON, P443
[8]  
Erdmann C.A., 2004, MUCOUS MEMBRANE LOWE
[9]   Worker performance and ventilation in a call center: analyses of work performance data for registered nurses [J].
Federspiel, CC ;
Fisk, WJ ;
Price, PN ;
Liu, G ;
Faulkner, D ;
Dibartolome, DL ;
Sullivan, DP ;
Lahiff, M .
INDOOR AIR, 2004, 14 :41-50
[10]  
Fisk W.J., 2010, CO2 monitoring for demand controlled ventilation in commercial buildings