An Approach to Improve the Penetration of Sustainable Energy Using Optimal Transformer Tap Control

被引:7
作者
Bae, Moonsung [1 ]
Lee, Hwanik [1 ]
Lee, Byongjun [1 ]
机构
[1] Korea Univ, Sch Elect Engn, Anam Campus,145 Anam Ro, Seoul 02841, South Korea
关键词
reactive power reserve; sensitivity analysis; on-load tap-changers; sustainable energy penetration; VOLTAGE CONTROL; POWER; SYSTEM; COORDINATION; OLTC;
D O I
10.3390/su9091536
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A method to secure the generator reactive power reserve by adjusting the transformer tap to improve the power system penetration of renewable energy has been proposed in this study. The tap is adjusted based on the voltage and reactive power sensitivity in the power system network. That is, the transformer tap sensitivity is calculated and analyzed to adjust the tap variation to gain sufficient or the least necessary amount of reactive power reserve. This method can be effective for generators without any margins in the reserves. The optimization problem based on the calculated sensitivities and effectiveness are presented. The optimum solution derived from such a problem provides the minimum control amount necessary to maintain the system voltage and dynamic reactive power reserve at their pre-specified levels to improve the power system acceptability of renewable energy. To demonstrate the effectiveness of the method proposed, a simulation has been performed for an IEEE-25 bus system. The results from simulations prove that the voltage has been well maintained while securing a dynamic reactive power reserve through optimal control based on the sensitivity analysis.
引用
收藏
页数:15
相关论文
共 34 条
[1]  
ALI M, 2017, SUSTAINABILITY BASEL, V9
[2]  
[Anonymous], 2010, IEEE PES GEN M
[3]  
Bae M., STUDY EFFICIENT CALC
[4]   Coordination Between OLTC and SVC for Voltage Regulation in Unbalanced Distribution System Distributed Generation [J].
Daratha, Novalio ;
Das, Biswarup ;
Sharma, Jaydev .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (01) :289-299
[5]   Improving voltage stability by reactive power reserve management [J].
Dong, F ;
Chowdhury, BH ;
Crow, ML ;
Acar, L .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (01) :338-345
[6]   Voltage versus var/power-factor regulation on synchronous generators [J].
Eberly, TW ;
Schaefer, RC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (06) :1682-1687
[7]   Increasing renewable penetration on islanded networks through active network management: a case study from Shetland [J].
Gill, Simon ;
Dolan, Michael ;
Emhemed, Abdullah ;
Kockar, Ivana ;
Barnacle, Malcolm ;
Ault, Graham ;
Mathieson, Colin .
IET RENEWABLE POWER GENERATION, 2015, 9 (05) :453-465
[8]  
Huh JH, 2016, JOINT INT CONF SOFT, P736, DOI [10.1109/SCIS-ISIS.2016.0161, 10.1109/SCIS&ISIS.2016.192]
[9]   Design and Android Application for Monitoring System Using PLC for ICT-Integrated Fish Farm [J].
Huh, Jun-Ho .
ADVANCED MULTIMEDIA AND UBIQUITOUS ENGINEERING: FUTURETECH & MUE, 2016, 393 :617-625
[10]  
Huh Jun-Ho, 2015, SERSC ASTL, V94, P57