MEASUREMENT AND ANALYSIS OF ELECTRIC AND MAGNETIC FIELD STRENGTH IN GRID-TIED PHOTOVOLTAIC POWER SYSTEM COMPONENTS

被引:0
作者
Bedeloglu, Merve [1 ,2 ]
Il, Niyazi [1 ]
Ates, Kayhan [1 ]
Ozen, Sukru [1 ]
机构
[1] Akdeniz Univ, Dept Elect & Elect Engn, Antalya, Turkey
[2] Alanya Alaaddin Keykubat Univ, ALTSO Vocat Sch, Antalya, Turkey
关键词
EXPOSURE;
D O I
10.1093/rpd/ncab070
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this study, electric field and magnetic field strengths at 50 Hz are measured in a solar power plant located far from residential areas, and the measurement results near various sources of the electric and magnetic fields in the power plant are presented. Although the measured values for the electric field caused by the solar panel range between 0.07 and 1.33 V/m, the measured values for the magnetic field by the solar panel range between 0.037 and 0.19 mu T. In front of the inverter, the measured value of the electric field reaches 0.7 V/m, whereas the measured value of the magnetic field reaches 2.2 mu T. The results are presented and evaluated in light of the exposure limits to electromagnetic fields published by international organisations.
引用
收藏
页码:57 / 64
页数:8
相关论文
共 14 条
[11]   Measuring electromagnetic fields (EMF) around wind turbines in Canada: is there a human health concern? [J].
McCallum, Lindsay C. ;
Aslund, Melissa L. Whitfield ;
Knopper, Loren D. ;
Ferguson, Glenn M. ;
Ollson, Christopher A. .
ENVIRONMENTAL HEALTH, 2014, 13
[12]   Evaluation and measurement of magnetic field exposure at a typical high-voltage substation and its power lines [J].
Ozen, S. .
RADIATION PROTECTION DOSIMETRY, 2008, 128 (02) :198-205
[13]  
Safigianni AS, 2013, PR ELECTROMAGN RES S, P1908
[14]   Electric and Magnetic Field Measurements in a High Voltage Center [J].
Safigianni, Anastasia S. ;
Spyridopoulos, Anastasios I. ;
Kanas, Vasilis L. .
ANNALS OF OCCUPATIONAL HYGIENE, 2012, 56 (01) :18-24