MEASUREMENT AND ANALYSIS OF ELECTRIC AND MAGNETIC FIELD STRENGTH IN GRID-TIED PHOTOVOLTAIC POWER SYSTEM COMPONENTS

被引:0
作者
Bedeloglu, Merve [1 ,2 ]
Il, Niyazi [1 ]
Ates, Kayhan [1 ]
Ozen, Sukru [1 ]
机构
[1] Akdeniz Univ, Dept Elect & Elect Engn, Antalya, Turkey
[2] Alanya Alaaddin Keykubat Univ, ALTSO Vocat Sch, Antalya, Turkey
关键词
EXPOSURE;
D O I
10.1093/rpd/ncab070
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this study, electric field and magnetic field strengths at 50 Hz are measured in a solar power plant located far from residential areas, and the measurement results near various sources of the electric and magnetic fields in the power plant are presented. Although the measured values for the electric field caused by the solar panel range between 0.07 and 1.33 V/m, the measured values for the magnetic field by the solar panel range between 0.037 and 0.19 mu T. In front of the inverter, the measured value of the electric field reaches 0.7 V/m, whereas the measured value of the magnetic field reaches 2.2 mu T. The results are presented and evaluated in light of the exposure limits to electromagnetic fields published by international organisations.
引用
收藏
页码:57 / 64
页数:8
相关论文
共 14 条
  • [1] American Conference of Governmental Industrial Hygienists (ACGIH), 2021, TLVs and BEIs based on the documentation of Threshold limit values for chemical substances and physical agents and biological exposure indices
  • [2] Measurement of the magnetic fields of high-voltage substations (230 kV) in Tehran (Iran) and comparison with the ACGIH treshold limit values
    Fard, Mahdieh Sharifi
    Nasiri, Parvin
    Monazzam, Mohammad Reza
    [J]. RADIATION PROTECTION DOSIMETRY, 2011, 145 (04) : 421 - 425
  • [3] Assessment of occupational exposure to magnetic fields in high-voltage substations (154/34.5 kV)
    Helhel, S.
    Ozen, S.
    [J]. RADIATION PROTECTION DOSIMETRY, 2008, 128 (04) : 464 - 470
  • [4] IEEE Institute of Electrical and Electronics Engineers, 2019, IEEE Std, DOI [10.1109/IEEESTD.2019.8859679, DOI 10.1109/IEEESTD.2019.8859679]
  • [5] Ifong Wu, 2015, IEEE Electromagnetic Compatibility Magazine, V4, P73, DOI 10.1109/MEMC.2015.7204055
  • [6] Il N., 2015, 4 EL TES UL K SERG I, P67
  • [7] ICNIRP STATEMENT-GUIDELINES FOR LIMITING EXPOSURE TO TIME-VARYING ELECTRIC AND MAGNETIC FIELDS (1 HZ TO 100 KHZ)
    不详
    [J]. HEALTH PHYSICS, 2010, 99 (06): : 818 - 836
  • [8] Juswardy B., 2011, ELECTROMAGNETIC COMP, P1
  • [9] Karami H, 2015, 2015 1st URSI Atlantic Radio Science Conference (URSI AT-RASC)
  • [10] Loschi H. J., 2018, Journal of Clean Energy Technologies, V6, P125, DOI 10.18178/jocet.2018.6.2.447