Experimental investigation of condensation in energy recovery ventilators

被引:8
作者
Abadi, Iman Rahgozar [1 ]
Aminian, Behzad [1 ]
Nasr, Mohammad Rafati [2 ]
Huizing, Ryan [2 ]
Green, Sheldon [1 ]
Rogak, Steven [1 ]
机构
[1] Univ British Columbia, Dept Mech Engn, 2329 West Mall, Vancouver, BC V6T 1Z4, Canada
[2] Core Energy Recovery Solut, 1455 East Georgia St, Vancouver, BC V5L 2A9, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Energy recovery ventilator; Total heat exchanger; Energy exchanger; Heat and moisture exchanger; Condensation; Membrane; AIR HEAT-EXCHANGER; MASS-TRANSFER; EXPERIMENTAL VALIDATION; ENTHALPY EXCHANGERS; PERFORMANCE; MODEL; MOISTURE; PLATE; CONSUMPTION; IMPROVEMENT;
D O I
10.1016/j.enbuild.2021.111732
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Membrane-based Energy Recovery Ventilators (ERV) have become an important part of modern ventilation systems for commercial and residential buildings due to their high sensible and latent effectiveness. Using ERVs in winter conditions, however, can result in condensation and frost formation. Whereas frost formation requires extremely low temperatures, condensation can occur even in mild winter weather conditions. In this study, a widely used ERV is experimentally tested under various indoor and outdoor operating conditions. Short time tests are used to determine the onset of condensation while long time tests are used to investigate the effect of channel blockage due to condensation on pressure drop and effectiveness of the ERV. The presence of condensation is inferred from visual observation of water in the exchanger, investigation of the sensible and latent effectiveness, and measurements of pressure drop over the exchanger. It is shown that condensation increases the sensible effectiveness of the supply side and decreases the sensible effectiveness of the exhaust side. Additionally, the latent effectiveness of both air streams increases when condensation occurs, although the increase in exhaust side latent effectiveness is more significant. Increasing the relative humidity and temperature of the indoor air increases the possibility of condensation and its rate, while increasing flowrate only increases the rate of condensation and does not affect its onset. Finally, the accumulation of water in the channels significantly increases the pressure drop in the exhaust side while it does not significantly impact the effectiveness. (C) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:13
相关论文
共 41 条
[1]  
Abadi I. Rahgozar, J APPL THERM ENG
[2]  
Abadi I. Rahgozar, J MEMBRANE SCI, V2021
[3]   Annual evaluation of energy, environmental and economic performances of a membrane liquid desiccant air conditioning system with/without ERV [J].
Abdel-Salam, Ahmed H. ;
Simonson, Carey J. .
APPLIED ENERGY, 2014, 116 :134-148
[4]   Performance of energy recovery ventilators under different climatic regions [J].
Al-Waked, Rafat ;
Bani Mostafa, Diala ;
Nasif, Mohammad S. .
ENERGY EFFICIENCY, 2021, 14 (01)
[5]   Frost formation in the cross-flow plate heat exchanger for energy recovery [J].
Anisimov, Sergey ;
Jedlikowski, Andrzej ;
Pandelidis, Demis .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 90 :201-217
[6]  
Baker R.W., 2012, Membrane Technology and Applications, DOI [DOI 10.1002/9781118359686, 10.1002/9781118359686]
[7]  
Bradley E.P.R.C.B., 1989, ASHRAE T, V95, P454
[8]   Heat and mass transfer in cross-flow air-to-air membrane heat exchanger in heating mode [J].
Deshko, Valerii I. ;
Karvatskii, Anton Ya ;
Sukhodub, Iryna O. .
APPLIED THERMAL ENGINEERING, 2016, 100 :133-145
[9]  
Engarnevis A., 2018, Impact of humidity, temperature, and particulate fouling on membrane-based energy exchangers
[10]   Heat and mass transfer modeling in enthalpy exchangers using asymmetric composite membranes [J].
Engarnevis, Amin ;
Huizing, Ryan ;
Green, Sheldon ;
Rogak, Steven .
JOURNAL OF MEMBRANE SCIENCE, 2018, 556 :248-262