Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model

被引:137
|
作者
Ge, T. S. [1 ]
Dai, Y. J. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
Desiccant cooling; Heat exchanger; Mathematical model; Performance; Operation time; MOISTURE TRANSPORT; BED DEHUMIDIFIER; DESICCANT;
D O I
10.1016/j.enconman.2010.12.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
Desiccant coated heat exchanger (DCHE) system can handle latent and sensible load simultaneously by removing the released adsorption heat in dehumidification process. The system can also be driven by low grade thermal energy such as solar energy. In this paper, a dynamic one-dimensional mathematical model validated by experimental data is established to predict the performance of DCHE system, using conventional silica gel as desiccant material. Cooling performance of DCHE system is calculated under ARI (American Air-conditioning and Refrigeration Institute) summer and humid conditions. Simulated results show that the operation time in dehumidification process is a crucial factor for cooling capacity of DCHE system, which can be enhanced by eliminating the initial period with higher outlet air temperature, the largest cooling power of DCHE system increase from 2.6 kW to 3.5 kW by eliminating first 50 s of operation time under ARI summer condition. The results also prove that the system can provide cooling power to indoor condition with selective operation time when regeneration temperature varies from 50 degrees C to 80 degrees C. Besides, the model is adopted to analyze the effects of some structural parameters on system performance under simulated condition. The system performs well in smaller cobber tube external diameter condition, while both transient heat and mass transfer capacity can be enhanced under the condition of smaller distance between the fins. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2329 / 2338
页数:10
相关论文
共 46 条
  • [41] Numerical study of the cold finned-tube bundle heat exchanger under natural convection for a novel passive displacement cooling system
    Guo, Shuai
    Cheng, Kai Xian
    Lee, Poh Seng
    BUILDING AND ENVIRONMENT, 2023, 233
  • [42] Experimental study and analysis of solar based winter air conditioning system using desiccant coated heat exchanger
    Nain, Sunil
    Parinam, Anuradha
    Kajal, Sanjay
    MATERIALS TODAY-PROCEEDINGS, 2021, 46 : 9938 - 9943
  • [43] On-line model-based performance monitoring of a shell-and-tube type heat exchanger using steam and water
    Wakui, Tetsuya
    Yokoyama, Ryohei
    ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (10) : 2669 - 2677
  • [44] Configuration optimization for offset strip plate-fin heat exchanger using a method of PID-based search algorithm driving design indicators mathematical model
    Xu, Zhe
    Yu, Zongling
    Ning, Xin
    Zhao, Changyin
    Nie, Fuquan
    CASE STUDIES IN THERMAL ENGINEERING, 2025, 68
  • [45] Study on multi-stream plate fin heat exchanger coupled with ortho-para hydrogen conversion based on distributed parameter model
    Li, Ke
    Li, Chaolong
    Wen, Jian
    Chen, Qiang
    Li, Yanzhong
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2023, 48 (85) : 33315 - 33334
  • [46] Energy storage performance improvement of phase change materials-based triplex-tube heat exchanger (TTHX) using liquid-solid interface-informed fin configurations
    Palmer, Ben
    Arshad, Adeel
    Yang, Yan
    Wen, Chuang
    APPLIED ENERGY, 2023, 333