Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model

被引:137
|
作者
Ge, T. S. [1 ]
Dai, Y. J. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
关键词
Desiccant cooling; Heat exchanger; Mathematical model; Performance; Operation time; MOISTURE TRANSPORT; BED DEHUMIDIFIER; DESICCANT;
D O I
10.1016/j.enconman.2010.12.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
Desiccant coated heat exchanger (DCHE) system can handle latent and sensible load simultaneously by removing the released adsorption heat in dehumidification process. The system can also be driven by low grade thermal energy such as solar energy. In this paper, a dynamic one-dimensional mathematical model validated by experimental data is established to predict the performance of DCHE system, using conventional silica gel as desiccant material. Cooling performance of DCHE system is calculated under ARI (American Air-conditioning and Refrigeration Institute) summer and humid conditions. Simulated results show that the operation time in dehumidification process is a crucial factor for cooling capacity of DCHE system, which can be enhanced by eliminating the initial period with higher outlet air temperature, the largest cooling power of DCHE system increase from 2.6 kW to 3.5 kW by eliminating first 50 s of operation time under ARI summer condition. The results also prove that the system can provide cooling power to indoor condition with selective operation time when regeneration temperature varies from 50 degrees C to 80 degrees C. Besides, the model is adopted to analyze the effects of some structural parameters on system performance under simulated condition. The system performs well in smaller cobber tube external diameter condition, while both transient heat and mass transfer capacity can be enhanced under the condition of smaller distance between the fins. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2329 / 2338
页数:10
相关论文
共 46 条
  • [21] Experimental investigation of silica gel coated heat exchanger air conditioning system based on graphene nanofluid solar collector
    Kumar, Jasvinder
    Kaushal, Rajneesh
    ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2024, 46 (01) : 2197 - 2211
  • [22] Experimental study on silica gel-LiCl composite desiccants for desiccant coated heat exchanger
    Zheng, X.
    Ge, T. S.
    Jiang, Y.
    Wang, R. Z.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 51 : 24 - 32
  • [23] Experimental Study on the Air-Side Heat Transfer Characteristics of a Spirally-Coiled Circular Fin-Tube Heat Exchanger According to Geometric Parameters
    Kang, Taehyung
    Lee, Mooyeon
    Kim, Yongchan
    Yun, Sungjung
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2010, 34 (05) : 515 - 522
  • [24] Experimental study of the effect of cyclic and stepped temperature and flow rate change operations on the solid particle/thermal oil fin-tube heat exchanger
    Ji, Mengting
    Lv, Laiquan
    Zhou, Hao
    JOURNAL OF ENERGY STORAGE, 2024, 103
  • [25] Feasible study of a self-cooled solid desiccant cooling system based on desiccant coated heat exchanger
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Li, Y.
    APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) : 281 - 290
  • [26] Performance study of desiccant coated heat exchanger air conditioning system in winter
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    ENERGY CONVERSION AND MANAGEMENT, 2016, 123 : 559 - 568
  • [27] A general simulation model for performance prediction of plate fin-and-tube heat exchanger with complex circuit configuration
    Ding, W. K.
    Fan, J. F.
    He, Y. L.
    Tao, W. Q.
    Zheng, Y. X.
    Gao, Y. F.
    Song, J.
    APPLIED THERMAL ENGINEERING, 2011, 31 (16) : 3106 - 3116
  • [28] An experimental study of the air-side performance of a novel louver spiral fin-and-tube heat exchanger
    Kiatpachai, Parinya
    Keawkamrop, Thawatchai
    Asirvatham, Lazarus Godson
    Mesgarpour, Mehrdad
    Dalkilic, Ahmet Selim
    Ahn, Ho Seon
    Mahian, Omid
    Wongwises, Somchai
    ALEXANDRIA ENGINEERING JOURNAL, 2022, 61 (12) : 9811 - 9818
  • [29] An experimental study on the offset-strip fin geometry optimization of a plate-fin heat exchanger based on the heat current model
    Hao, Jun-Hong
    Chen, Qun
    Ren, Jian-Xun
    Zhang, Meng-Qi
    Ai, Jing
    APPLIED THERMAL ENGINEERING, 2019, 154 : 111 - 119
  • [30] Analysis on solar energy powered cooling system based on desiccant coated heat exchanger using metal-organic framework
    Xu, F.
    Bian, Z. F.
    Ge, T. S.
    Dai, Y. J.
    Wang, C. H.
    Kawi, S.
    ENERGY, 2019, 177 : 211 - 221