Impacts of Corona Rings on the Insulation Performance of Composite Polymer Insulator Strings

被引:13
作者
Ilhan, S. [1 ]
Ozdemir, A. [1 ]
Ismailoglu, H. [2 ]
机构
[1] Istanbul Tech Univ, Dept Elect Engn, TR-34469 Istanbul, Turkey
[2] Kocaeli Univ, Dept Elect & Comp Engn, TR-41380 Kocaeli, Turkey
关键词
Composite insulator; corona ring; insulation performance; impulse voltages; AC voltage; arc distance; LARGE AIR GAPS; NONCERAMIC INSULATORS; ELECTRIC-FIELD; IMPULSE; FLASHOVER; STRENGTH;
D O I
10.1109/TDEI.2015.7116356
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Corona rings can improve the insulation performance of insulator strings because of their electric field grading property or can decrease the insulation performance due to their arc clearance reduction property. The resulting insulation performance of the string which is under the influence of those two conflicting effects depends on the corona ring parameter settings. Therefore, a detailed experimental work is required to determine the insulation performance for different types of test voltages under different ambient conditions. This paper presents the results of experimental studies regarding the effects of corona rings on the insulation performance of 380 kV non-ceramic V-insulator strings. Those effects and flashover routes were determined for lightning impulses, switching impulses and AC voltages. Corona ring diameter, corona tube diameter, and mounting height were selected as the ring design parameters. Experimental studies were performed for the strings including corona rings of different design parameters as well as for the ring free strings. Test results were discussed from discharge development physics point of view and optimal configuration was determined for the strings.
引用
收藏
页码:1605 / 1612
页数:8
相关论文
共 29 条
[1]  
[Anonymous], 1992, 3301 CIGREWG
[2]  
[Anonymous], IEEE987
[3]   SWITCHING SURGE STRENGTH OF LARGE AIR GAPS - PHYSICAL APPROACH [J].
CARRARA, G ;
THIONE, L .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (02) :512-524
[4]   GENERAL EXPRESSION FOR POSITIVE SWITCHING IMPULSE STRENGTH VALID UP TO EXTRA LONG AIR GAPS [J].
GALLET, G ;
LEROY, G ;
LACEY, R ;
KROMER, I .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (06) :1989-1993
[5]  
Gorur R.S., 1999, Outdoor Insulators
[6]   SWEDISH RESEARCH ON THE APPLICATION OF COMPOSITE INSULATORS IN OUTDOOR INSULATION [J].
GUBANSKI, S ;
HARTINGS, R .
IEEE ELECTRICAL INSULATION MAGAZINE, 1995, 11 (05) :24-31
[7]   Outdoor HV composite polymeric insulators [J].
Hackam, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (05) :557-585
[8]  
HAMMAM MSAA, 1991, PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, P981, DOI 10.1109/ICPADM.1991.172237
[9]  
Hileman AndrewR., 1999, Insulation Coordination for Power Systems
[10]  
IEC, 1996, IEC, 60071-2