Grid-Following Voltage Source Converters: Basic Schemes and Current Control Techniques to Operate With Unbalanced Voltage Conditions

被引:21
作者
Montero-Robina, Pablo [1 ]
Rouzbehi, Kumars [1 ]
Gordillo, Francisco [1 ]
Pou, Josep [2 ]
机构
[1] Univ Seville, Syst & Automat Dept, Seville, Spain
[2] Nanyang Technol Univ, Sch Elect & Elect Engn, Singapore 639798, Singapore
来源
IEEE OPEN JOURNAL OF THE INDUSTRIAL ELECTRONICS SOCIETY | 2021年 / 2卷
关键词
Voltage control; Power conversion; Phase locked loops; Industrial electronics; Frequency locked loops; Resonant frequency; Current control; Current controller; current reference generation; negative sequence; unbalanced grid; voltage source converter (VSC); STATIONARY FRAME; REPETITIVE CONTROLLER; POWER CONVERTERS; VSC-HVDC; PWM; SYNCHRONIZATION; PERFORMANCE; SYSTEMS; FILTER; PHASE;
D O I
10.1109/OJIES.2021.3121764
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The growing relevance of voltage source converters (VSCs), and the deep impact they have on the development and maintenance of the electrical grid, increase the necessity of further research on how to deal with nonideal grid conditions from the VSCs control. This paper is aimed to summarize the basic techniques and schemes that might be required for a grid-connected VSC to work under these conditions: grid synchronization schemes, sequence decomposition, current reference generation, and current controllers. At the same time, some alternative schemes that improves the basic ones are cited. Modelling and the two typical current controllers design and tuning under stationary and synchronous reference frames are also exhibited. Given the importance of the current control stage in the VSC behaviour, five control schemes, designed to track negative sequence currents, are shown and tested in simulation and experiments. According to the experiments, it is shown that the standard proportional-resonant controller achieves the best performance in negative sequence tracking due to the robustness of its non-ideal version, the improved implementation thanks to the delta operator, and the non-dependence on grid-synchronization schemes. Alternatively, one approach based on dual synchronous reference frame is also highlighted for easiness of implementation and good performance.
引用
收藏
页码:528 / 544
页数:17
相关论文
共 85 条
[1]  
Akagi H, 2017, Instantaneous power theory and applications to power conditioning
[2]  
Al-Shetwi A Q., 2015, ARPN J. Eng. Appl. Sci, V10, P9906
[3]   An overview of control approaches of inverter-based microgrids in islanding mode of operation [J].
Andishgar, Mohammad Hadi ;
Gholipour, Eskandar ;
Hooshmand, Rahmat-allah .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 80 :1043-1060
[4]   A control structure for PWM-controlled static synchronous compensators under unbalanced conditions and grid faults [J].
Babaei, Saman ;
Bhattacharya, Subhashish .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 71 :160-173
[5]   Decoupled dq-Current Control of Grid-Tied Voltage Source Converters Using Nonparametric Models [J].
Bahrani, Behrooz ;
Karimi, Alireza ;
Rey, Benoit ;
Rufer, Alfred .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (04) :1356-1366
[6]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[7]   Distributed Power-Generation Systems and Protection [J].
Blaabjerg, Frede ;
Yang, Yongheng ;
Yang, Dongsheng ;
Wang, Xiongfei .
PROCEEDINGS OF THE IEEE, 2017, 105 (07) :1311-1331
[8]   A new mathematical model and control of a three-phase AC-DC voltage source converter [J].
Blasko, V ;
Kaura, V .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1997, 12 (01) :116-123
[9]  
Boyra M., 2011, Proceedings of the 2011 14th European Conference on Power Electronics and Applications, P1
[10]   Digital controller based on delta operator for high-frequency DC-DC switching converters [J].
Chen, Nan ;
Wei, Tingcun ;
Shang, Ke ;
Wang, Renkai .
IET POWER ELECTRONICS, 2018, 11 (07) :1224-1230