Estimating the impact of indoor relative humidity on SARS-CoV-2 airborne transmission risk using a new modification of the Wells-Riley model

被引:61
作者
Aganovic, Amar [1 ]
Bi, Yang [2 ]
Cao, Guangyu [2 ]
Drangsholt, Finn [1 ]
Kurnitski, Jarek [3 ]
Wargocki, Pawel [4 ]
机构
[1] UiT Arctic Univ Norway, Dept Automat & Proc Engn, Tromso, Norway
[2] Norwegian Univ Sci & Technol NTNU, Dept Energy & Proc Engn, Trondheim, Norway
[3] Tallinn Univ Technol, REHVA Technol & Res Comm, Tallinn, Estonia
[4] Tech Univ Denmark, Dept Civil Engn, Copenhagen, Denmark
关键词
SARS-CoV-2; Virus airborne transmission; Ventilation; Relative humidity; Indoor environment; VIRAL LOAD; PROTEIN; SPREAD; GROWTH;
D O I
10.1016/j.buildenv.2021.108278
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A novel modified version of the Wells-Riley model was used to estimate the impact of relative humidity (RH) on the removal of respiratory droplets containing the SARS-CoV-2 virus by deposition through gravitational settling and its inactivation by biological decay; the effect of RH on susceptibility to SARS-CoV-2 was not considered. These effects were compared with the removal achieved by increased ventilation rate with outdoor air. Modeling was performed assuming that the infected person talked continuously for 60 and 120 min. The results of modeling showed that the relative impact of RH on the infection risk depended on the ventilation rate and the size range of virus-laden droplets. A ventilation rate of 0.5 ACH, the change of RH between 20% and 53% was predicted to have a small effect on the infection risk, while at a ventilation rate of 6 ACH this change had nearly no effect. On the contrary, increasing the ventilation rate from 0.5 ACH to 6 ACH was predicted to decrease the infection risk by half which is remarkably larger effect compared with that predicted for RH. It is thus concluded that increasing the ventilation rate is more beneficial for reducing the airborne levels of SARS-CoV-2 than changing indoor RH. Practical implications: The present results show that humidification to moderate levels of 40%-60% RH should not be expected to provide a significant reduction in infection risk caused by SARS-CoV-2, hence installing and running humidifiers may not be an efficient solution to reduce the risk of COVID-19 disease in indoor spaces. The results do however confirm that ventilation has a key role in controlling SARS-CoV-2 virus concentration in the air providing considerably higher benefits. The modified model developed in the present work can be used by public health experts, engineers, and epidemiologists when selecting different measures to reduce the infection risk from SARS-CoV-2 indoors allowing informed decisions concerning indoor environmental control.
引用
收藏
页数:14
相关论文
共 57 条
[1]  
Adams WC, 1993, MEASUREMENT BREATHIN
[2]  
[Anonymous], 2014, BUILD B
[3]   Size distribution of virus laden droplets from expiratory ejecta of infected subjects [J].
Anand, S. ;
Mayya, Y. S. .
SCIENTIFIC REPORTS, 2020, 10 (01)
[4]  
Beggs CB, 2003, INT J TUBERC LUNG D, V7, P1015
[5]   Relative humidity in droplet and airborne transmission of disease [J].
Bozic, Anze ;
Kanduc, Matej .
JOURNAL OF BIOLOGICAL PHYSICS, 2021, 47 (01) :1-29
[6]   Quantitative assessment of the risk of airborne transmission of SARS-CoV-2 infection: Prospective and retrospective applications [J].
Buonanno, G. ;
Morawska, L. ;
Stabile, L. .
ENVIRONMENT INTERNATIONAL, 2020, 145
[7]   Estimation of airborne viral emission: Quanta emission rate of SARS-CoV-2 for infection risk assessment [J].
Buonanno, G. ;
Stabile, L. ;
Morawska, L. .
ENVIRONMENT INTERNATIONAL, 2020, 141
[8]   A review of the performance of different ventilation and airflow distribution systems in buildings [J].
Cao, Guangyu ;
Awbi, Hazim ;
Yao, Runming ;
Fan, Yunqing ;
Siren, Kai ;
Kosonen, Risto ;
Zhang, Jianshun .
BUILDING AND ENVIRONMENT, 2014, 73 :171-186
[9]  
CEN,, 2019, 16798 CEN EN 1
[10]   Characterization of expiration air jets and droplet size distributions immediately at the mouth opening [J].
Chao, C. Y. H. ;
Wan, M. P. ;
Morawska, L. ;
Johnson, G. R. ;
Ristovski, Z. D. ;
Hargreaves, M. ;
Mengersen, K. ;
Corbett, S. ;
Li, Y. ;
Xie, X. ;
Katoshevski, D. .
JOURNAL OF AEROSOL SCIENCE, 2009, 40 (02) :122-133