Power Harmonics and Interharmonics Measurement Using Recursive Group-Harmonic Power Minimizing Algorithm

被引:107
作者
Lin, Hsiung Cheng [1 ]
机构
[1] Natl Chin Yi Univ Technol, Dept Elect Engn, Taichung 411, Taiwan
关键词
Discrete Fourier transform (DFT); group harmonics; harmonics; interharmonics; SYSTEM; FREQUENCY; FLICKER; TRACKING;
D O I
10.1109/TIE.2011.2157281
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The discrete Fourier transform (DFT) is still a widely used tool for analyzing and measuring both stationary and transient signals in power system harmonics. However, the misapplications of the DFT can lead to incorrect results caused by some problems such as an aliasing effect, spectral leakage, and picket-fence effect. A strategy of recursive group-harmonic power minimizing algorithm is developed for systemwide harmonic/interharmonic evaluation in power systems. The proposed algorithm can restore the dispersing spectral leakage energy caused by the DFT and regain its harmonic/interharmonic magnitude and respective frequency. Every iteration loop for harmonic/interharmonic evaluation can guarantee to be convergent using the proposed group-harmonic bin power algorithm. Consequently, not only high precision in integer harmonic measurement can be retained but also the interharmonics can be accurately identified, particularly under system frequency drift. The numerical example is presented to verify the proposed algorithm in terms of robust, fast, and precise performance.
引用
收藏
页码:1184 / 1193
页数:10
相关论文
共 47 条