Design and testing of 230 V inductive type of superconducting fault current limiter with an open core

被引:20
作者
Kozak, J [1 ]
Janowski, T [1 ]
Kozak, S [1 ]
Malinowski, H [1 ]
Wojtasiewicz, G [1 ]
Kondratowicz-Kucewicz, B [1 ]
机构
[1] Electrotech Inst Warsaw, Lab Supercond Technol, PL-20618 Lublin, Poland
关键词
HTS tube; open core; superconducting fault current limiter;
D O I
10.1109/TASC.2005.849444
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A single-phase, 230 V Superconducting Fault Current Limiter using two Bi2223 HTS tubes with the total critical current 2.5 kA situated in vacuum insulated cryostat has been described in this paper. We designed and manufactured the inductive SFCL with an open core as core shielded type acquired the optimal design parameters by using Finite Element Method. We tested the limiter performances at liquid nitrogen temperature 77 K. We proved that the performances of properly designed limiter with open core could be comparable to the limiter with closed core.
引用
收藏
页码:2031 / 2034
页数:4
相关论文
共 3 条
[1]   Physical and numerical models of superconducting fault current limiters [J].
Kozak, S ;
Janowski, T .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :2068-2071
[2]  
NIELSEN JN, APPL HTS FAULT CURRE
[3]   Modeling of the transient behavior of a resistive type high TC fault current limiter [J].
Petranovic, R ;
Miri, AM .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :2036-2039