Numerical and experimental evaluation on methods for parameter identification of thermal response tests

被引:4
作者
Wang Feng-hao [1 ]
Feng Chen-chen [1 ]
Yan Liang [2 ]
Wang Xin-ke [1 ]
机构
[1] Xi An Jiao Tong Univ, Bldg Energy Res Ctr, Xian 710049, Peoples R China
[2] Shanghai Architectural Design & Res Inst Co Ltd, Shanghai 200063, Peoples R China
来源
JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY | 2012年 / 19卷 / 03期
关键词
ground source heat pump; thermal response; parameter identification method; numerical simulation; HEAT-EXCHANGER; MODEL;
D O I
10.1007/s11771-012-1077-3
中图分类号
TF [冶金工业];
学科分类号
0806 ;
摘要
Several parameter identification methods of thermal response test were evaluated through numerical and experimental study. A three-dimensional finite-volume numerical model was established under the assumption that the soil thermal conductivity had been known in the simulation of thermal response test. The thermal response curve was firstly obtained through numerical calculation. Then, the accuracy of the numerical model was verified with measured data obtained through a thermal response test. Based on the numerical and experimental thermal response curves, the thermal conductivity of the soil was calculated by different parameter identification methods. The calculated results were compared with the assumed value and then the accuracy of these methods was evaluated. Furthermore, the effects of test time, variable data quality, borehole radius, initial ground temperature, and heat injection rate were analyzed. The results show that the method based on cylinder-source model has a low precision and the identified thermal conductivity decreases with an increase in borehole radius. For parameter estimation, the measuring accuracy of the initial temperature of the deep ground soil has greater effect on identified thermal conductivity.
引用
收藏
页码:816 / 823
页数:8
相关论文
共 22 条
  • [1] ASHRAE, 2007, 2007 ASHRAE HDB HVAC
  • [2] Austin W.A., 1998, DEV IN SITU SYSTEM M
  • [3] Ground water level influence on thermal response test in Adana, Turkey
    Bozdag, S.
    Turgut, B.
    Paksoy, H.
    Dikici, D.
    Mazman, M.
    Evliya, H.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (07) : 629 - 633
  • [4] CARSLAW HS, 1959, CONDUCTION HEAT SOLI, P57
  • [5] EKLlOF C, 1996, TED MOBILE EQUIPMENT
  • [6] First in situ determination of the thermal performance of a U-pipe borehole heat exchanger, in Cyprus
    Florides, Georglos
    Kalogirou, Soteris
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (2-3) : 157 - 163
  • [7] An improved thermal response test for U-tube ground heat exchanger based on optical fiber thermometers
    Fujii, Hikari
    Okubo, Hiroaki
    Nishi, Keita
    Itoi, Ryuichi
    Ohyama, Kunio
    Shibata, Kazuo
    [J]. GEOTHERMICS, 2009, 38 (04) : 399 - 406
  • [8] IGSHPA (international ground source heat pump association), 2007, CLOS LOOP GEOTH HEAT, P1
  • [9] Ingersoll L., 1948, ASHRAE T, V54, P339
  • [10] Katsura T., 2006, P 10 EN CONS THERM E, P1