Monitoring and Assessment of Indoor Environmental Conditions after the Implementation of COVID-19-Based Ventilation Strategies in an Educational Building in Southern Spain

被引:23
作者
Aguilar, Antonio J. [1 ]
De la Hoz-torres, Maria L. [1 ]
Martinez-Aires, M. Dolores [2 ]
Ruiz, Diego P. [1 ]
机构
[1] Univ Granada, Dept Appl Phys, Av Severo Ochoa S-N, Granada 18071, Spain
[2] Univ Granada, Dept Bldg Construct, Av Severo Ochoa S-N, Granada 18071, Spain
关键词
indoor environmental quality; buildings; natural ventilation; COVID-19; IEQ; educational buildings; construction; AIR-QUALITY; THERMAL COMFORT; PERFORMANCE; HEALTH; SCHOOLS; NOISE; ACHIEVEMENT; POLLUTANTS; CLASSROOMS; IMPACT;
D O I
10.3390/s21217223
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Since students and teachers spend much of their time in educational buildings, it is critical to provide good levels of indoor environmental quality (IEQ). The current COVID-19 pandemic has shown that maintaining a good indoor air quality level is an effective measure to control the transmission of the SARS-CoV-2 virus. This study used sensors to monitor key IEQ factors and assess several natural ventilation scenarios in a classroom of the University of Granada. Subsequently, the IEQ factors (temperature, relative humidity, CO2 concentration, acoustic environment, and air velocity) were evaluated for the selected ventilation scenarios in the occupied classroom, and the field monitoring was carried out in two different assessment periods, winter and summer. The obtained results show that the CO2 concentration levels were well below the recommended limits. However, the maintenance of the recommended thermal and acoustic IEQ factors was significantly affected by the natural ventilation strategies (temperature and relative humidity values were very close to the outside values, and the background sound pressure level was over 35 dBA during the entire assessment). The proper measurements and careful selection of the appropriate ventilation scenarios become of utmost importance to ensure that the ventilation rates required by the health authorities are achieved.
引用
收藏
页数:16
相关论文
共 58 条
  • [1] Alfano F.d.A., 2010, REHVA J, V13, P1
  • [2] Study effects of school noise on learning achievement and annoyance in Assiut city, Egypt
    Ali, Sayed Abas Ai
    [J]. APPLIED ACOUSTICS, 2013, 74 (04) : 602 - 606
  • [3] Allen J., 2020, Healthy buildings
  • [4] Natural ventilation and indoor air quality in educational buildings: experimental assessment and improvement strategies
    Almeida, Ricardo M. S. F.
    Pinto, Manuel
    Pinho, Paulo G.
    de Lemos, Luis T.
    [J]. ENERGY EFFICIENCY, 2017, 10 (04) : 839 - 854
  • [5] Effects of the COVID-19 Pandemic on Indoor Air Quality and Thermal Comfort of Primary Schools in Winter in a Mediterranean Climate
    Alonso, Alicia
    Llanos, Jesus
    Escandon, Rocio
    Sendra, Juan J.
    [J]. SUSTAINABILITY, 2021, 13 (05) : 1 - 17
  • [6] [Anonymous], 2011, P 3 INT YOUTH C EN L
  • [7] [Anonymous], 2014, GUIDELINES HLTH ENV, DOI DOI 10.2788/89936
  • [8] ANSI/ASA, 2010, S12602010 ANSIASA 1
  • [9] The impact of classroom design on pupils' learning: Final results of a holistic, multi-level analysis
    Barrett, Peter
    Davies, Fay
    Zhang, Yufan
    Barrett, Lucinda
    [J]. BUILDING AND ENVIRONMENT, 2015, 89 : 118 - 133
  • [10] Ventilation rates in recently constructed US school classrooms
    Batterman, S.
    Su, F. -C.
    Wald, A.
    Watkins, F.
    Godwin, C.
    Thun, G.
    [J]. INDOOR AIR, 2017, 27 (05) : 880 - 890