The Effectiveness of Compensated Passive Loops for Mitigating Underground Power Cable Magnetic Fields

被引:13
|
作者
del Pino Lopez, Juan Carlos [1 ]
Cruz Romero, Pedro [1 ]
机构
[1] Univ Seville, Dept Elect Engn, Seville 41092, Spain
关键词
Compensated loop; enchained loops; magnetic field; mitigation; OPTIMIZATION; REDUCTION; LINES;
D O I
10.1109/TPWRD.2009.2039150
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes the possibility of using compensated passive loops to obtain a high mitigation effectiveness of the magnetic field generated by underground single-core cables. With that aim, several loops arrangements are simulated in a case study, including new ones called enchained loops, whose geometry reminds short-circuited conductors at both ends, but with the advantage of requiring smaller compensating capacitors. The results show a drastic spot reduction in several configurations, but with the drawback of high sensitivity to parameters. This aspect should be taken into account in the final design, so a design procedure is proposed that includes measures to alleviate this problem. Eventually, a comparison using shielding with high-conductivity material is provided.
引用
收藏
页码:674 / 683
页数:10
相关论文
共 45 条
  • [1] Passive loop-based mitigation of magnetic fields from underground power cable
    Cruz Romero, Pedro
    Hoeffelman, Jean
    Del Pino López, Juan Carlos
    IEEE Latin America Transactions, 2008, 6 (01) : 59 - 65
  • [2] Passive mitigation of stray magnetic fields generated by underground power lines
    Canova, Aldo
    Giaccone, Luca
    Lavecchia, Giuseppe
    Ribaldone, Paolo
    2017 1ST IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2017 17TH IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2017,
  • [3] Thermal Effects on the Design of Passive Loops to Mitigate the Magnetic Field Generated by Underground Power Cables
    del Pino Lopez, Juan Carlos
    Cruz Romero, Pedro
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) : 1718 - 1726
  • [4] Mitigation of Magnetic Fields in Dynamic Wireless Power Transfer Systems through Passive Compensation Loops
    Campi, Tommaso
    Cruciani, Silvano
    Maradei, Francesca
    Feliziani, Mauro
    PROCEEDINGS OF 2024 IEEE WIRELESS POWER TECHNOLOGY CONFERENCE AND EXPO, WPTCE, 2024, : 562 - 565
  • [5] Survey of underground cable generated magnetic fields in a residential subdivision
    Karady, George G.
    Holbert, Keith E.
    Adhikari, Sanket G.
    Dyer, Michael L.
    2008 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2008, : 240 - +
  • [6] Evaluation of the magnetic fields generated by underground cable and overhead power transmission lines using calculation models
    Bevitori, P
    Ravaioli, A
    ELECTRICITY AND MAGNETISM IN BIOLOGY AND MEDICINE, 1999, : 335 - 338
  • [7] Precise Positioning of the Underground Power Cable by Magnetic Field Detection
    Huang, Xuancheng
    Wang, Wei
    Lv, Zepeng
    Meng, Yongpeng
    Yuan, Chao
    Feng, Jianbao
    2019 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2019, : 702 - 705
  • [8] Detection of Underground Power Cable Route Using Magnetic Field
    Jahromy, Mehrdad Froodi
    Ostovarzadeh, Mohamad Hosein
    Davarani, Roohalamin Zeinali
    2017 IEEE 4TH INTERNATIONAL CONFERENCE ON KNOWLEDGE-BASED ENGINEERING AND INNOVATION (KBEI), 2017, : 533 - 538
  • [9] Analysis of electric and magnetic fields distribution and safe work zone of 154 kV power line in underground power cable tunnel
    Seong, Minyoung
    Kim, Doo Hyun
    Kim, Sung Chul
    Safety Science, 2021, 133
  • [10] Analysis of electric and magnetic fields distribution and safe work zone of 154 kV power line in underground power cable tunnel
    Seong, Minyoung
    Kim, Doo Hyun
    Kim, Sung Chul
    SAFETY SCIENCE, 2021, 133