Frequency Response Measurement of a Power Transformer

被引:0
作者
Ariastina, W. G. [1 ]
Kumara, I. N. S. [1 ]
Partha, C. G. Indra [1 ]
Arjana, I. G. Dyana [1 ]
机构
[1] Udayana Univ, Dept Elect & Comp Engn, Bali 80362, Indonesia
来源
2015 INTERNATIONAL CONFERENCE QUALITY IN RESEARCH (QIR) | 2015年
关键词
core and winding fault; power transformer; condition monitoring; SFRA;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a field experience in condition monitoring of a power transformer using SFRA technique. A design based comparison approach of the SFRA test results is discussed in the paper. In order to verify the latest condition of the transformer, the SFRA test was complemented with DGA and PD tests. The SFRA test results indicated that there is an abnormality within the transformer windings. The PD test results confirmed this interpretation, where very large ultrasonic impulses were detected. A series of DGA tests have showed that there is an early stage degradation of the insulating paper, which may be associated with fault within the transformer windings. The field experience showed that the monitoring approach has been very useful in indicating the possible occurrence of failure within the transformer structure.
引用
收藏
页码:102 / 105
页数:4
相关论文
共 50 条
  • [41] Rapid Measurement of Power Transformer Winding DC Resistance
    Luo, Xiaofei
    Xia, Xian
    Wu, Kaijun
    MEASUREMENT TECHNOLOGY AND ENGINEERING RESEARCHES IN INDUSTRY, PTS 1-3, 2013, 333-335 : 22 - 26
  • [42] Reflection of Tum to Tum Fault on a Transformer Frequency Response
    Ahour, J. Nosratian
    Shabihi, F.
    Fakher, A. Ahmadi
    2016 21ST CONFERENCE ON ELECTRICAL POWER DISTRIBUTION NETWORKS CONFERENCE (EPDC), 2016, : 60 - 63
  • [43] Efficiency Comparison of Solid-State Transformer and Low-Frequency Power Transformer
    Joshi, Archit
    Nath, Shabari
    2020 3RD INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS CLEAN ENERGY TECHNOLOGIES (ICEPE 2020), 2021,
  • [44] Toward Reliable Interpretation of Power Transformer Sweep Frequency Impedance Signatures: Experimental Analysis
    Zhao, Xiaozhen
    Yao, Chenguo
    Zhang, Cheng
    Abu-Siada, A.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2018, 34 (02) : 40 - 51
  • [45] Automatic Detection of Frequency Ranges of Power Transformer Transfer Functions for Evaluation by Mathematical Indicators
    Gonzales, J. C.
    Mombello, E. E.
    2012 SIXTH IEEE/PES TRANSMISSION AND DISTRIBUTION: LATIN AMERICA CONFERENCE AND EXPOSITION (T&D-LA), 2012,
  • [46] Evaluation of numerical indices for the assessment of transformer frequency response
    Samimi, Mohammad Hamed
    Tenbohlen, Stefan
    Akmal, Amir Abbas Shayegani
    Mohseni, Hossein
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (01) : 218 - 227
  • [47] Power Flow Estimation based on Power Transformer Plate Data and Voltage Measurement
    Passos, Frederico Oliveira
    de Carvalho Filho, Jose Maria
    2014 IEEE 16TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP), 2014, : 352 - 356
  • [48] Transformer tests, frequency domain spectroscopy and frequency sweep response analysis method
    Maya Izurieta, Nestor Xavier
    Vasquez Restrepo, Luis Alberto
    INGENIUS-REVISTA DE CIENCIA Y TECNOLOGIA, 2011, (05): : 55 - 62
  • [49] Novel method for detection of transformer winding faults using Sweep Frequency Response Analysis
    Singh, Jashandeep
    Sood, Yog Raj
    Verma, Piush
    Jarial, Raj Kumar
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 2949 - +
  • [50] Power Transformer Inrush Current Analysis: Simulation, Measurement and Effects
    Nitu, Maria-Cristina
    Nicolae, Ileana-Diana
    Dina, Livia-Andreea
    Mircea, Paul-Mihai
    APPLIED SCIENCES-BASEL, 2024, 14 (23):