Robust operation for minimizing power consumption of data centers with flexible substation integration

被引:24
作者
Ji, Haoran [1 ]
Chen, Sirui [1 ]
Yu, Hao [1 ]
Li, Peng [1 ]
Yan, Jinyue [2 ]
Song, Jieying [3 ]
Wang, Chengshan [1 ]
机构
[1] Tianjin Univ, Key Lab Smart Grid, Minist Educ, Tianjin 300072, Peoples R China
[2] Malardalen Univ, Sch Business Soc & Engn, S-72123 Vasteras, Sweden
[3] Global Energy Interconnect Res Inst State Grid, Beijing 100000, Peoples R China
关键词
Data centers; Flexible substation (FS); Minimizing power consumption; Distributionally robust optimization (DRO); Workload uncertainty; INTERNET DATA CENTERS; ENERGY; MANAGEMENT; SYSTEM; OPTIMIZATION; MINIMIZATION; STRATEGY; RESERVE; COST;
D O I
10.1016/j.energy.2022.123599
中图分类号
O414.1 [热力学];
学科分类号
摘要
The rapid development of digital economy has led to a dramatic increasement of internet data centers (IDCs), which consume a large amount of electricity. The diverse data-processing demands, high power consumption and workload uncertainty put forward a high requirement for the economical and secure operation of IDCs. As information technology (IT) devices are driven by direct current (DC), flexible substation (FS) has been gradually utilized to provide DC power for IDCs. This paper proposes robust operation strategies for minimizing IDC power consumption with FS integration. First, the linearized IDC power consumption model based on the technology of dynamic voltage and frequency scaling (DVFS) is proposed to describe the operating state of IT devices. Then, considering the FS-based coordinated operation of IDC, photovoltaic (PV) station and energy storage system (ESS), the deterministic power consumption minimization model of IDCs is established. Considering the workload uncertainty, the operation strategies based on distributionally robust optimization (DRO) for IDCs are further proposed. Finally, the effectiveness of proposed method is validated on a modified practical network with IDCs integrated. Results show that through the dispatch of workload and power flow regulation of FS, the power consumption and dropping workload of IDCs are effectively reduced.(c) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:13
相关论文
共 34 条
  • [1] Minimizing SLA violation and power consumption in Cloud data centers using adaptive energy-aware algorithms
    Zhou, Zhou
    Abawajy, Jemal
    Chowdhury, Morshed
    Hu, Zhigang
    Li, Keqin
    Cheng, Hongbing
    Alelaiwi, Abdulhameed A.
    Li, Fangmin
    FUTURE GENERATION COMPUTER SYSTEMS-THE INTERNATIONAL JOURNAL OF ESCIENCE, 2018, 86 : 836 - 850
  • [2] Demand Response in Data Centers: Integration of Server Provisioning and Power Procurement
    Kwon, Soongeol
    Ntaimo, Lewis
    Gautam, Natarajan
    IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (05) : 4928 - 4938
  • [3] The Flexible Operation of Coal Power and Its Renewable Integration Potential in China
    Na, Chunning
    Pan, Huan
    Zhu, Yuhong
    Yuan, Jiahai
    Ding, Lixia
    Yu, Jungang
    SUSTAINABILITY, 2019, 11 (16)
  • [4] Minimizing the operation cost of distributed green data centers with energy storage under carbon capping
    He, Huaiwen
    Shen, Hong
    JOURNAL OF COMPUTER AND SYSTEM SCIENCES, 2021, 118 : 28 - 52
  • [5] Robust Integration of High-Level Dispatchable Renewables in Power System Operation
    Ye, Hongxing
    Wang, Jianhui
    Ge, Yinyin
    Li, Jia
    Li, Zuyi
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (02) : 826 - 835
  • [6] Minimizing Energy Consumption of Smart Grid Data Centers using Cloud Computing
    Tayeb, Shahab
    Mirnabibaboli, Miresmaeil
    Chato, Lina
    Latifi, Shahram
    2017 IEEE 7TH ANNUAL COMPUTING AND COMMUNICATION WORKSHOP AND CONFERENCE IEEE CCWC-2017, 2017,
  • [7] Minimizing the power consumption of a clapper-type dc electromagnet in intermittent operation
    Zaitsev Y.M.
    Ivanov I.P.
    Petrov O.A.
    Prikazshchikov A.V.
    Russova N.V.
    Svintsov G.P.
    Russian Electrical Engineering, 2015, 86 (08) : 474 - 478
  • [8] Resilient Power Systems Operation with Offshore Wind Farms and Cloud Data Centers
    Liu, Shengwei
    Li, Yuanzheng
    Liu, Xuan
    Zhao, Tianyang
    Wang, Peng
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2023, 9 (06): : 1985 - 1998
  • [9] On Architecture Design, Congestion Notification, TCP Incast and Power Consumption in Data Centers
    Zhang, Yan
    Ansari, Nirwan
    IEEE COMMUNICATIONS SURVEYS AND TUTORIALS, 2013, 15 (01): : 39 - 64
  • [10] Exploiting Renewable Energy and UPS Systems to Reduce Power Consumption in Data Centers
    Peng, Xiaopu
    Bhattacharya, Tathagata
    Cao, Ting
    Mao, Jianzhou
    Tekreeti, Taha
    Qin, Xiao
    BIG DATA RESEARCH, 2022, 27