Investigation on X-Radiation for 126 kV Vacuum Interrupters

被引:3
作者
Yan Jing [1 ]
Liu Zhiyuan [1 ]
Geng Yingsan [1 ]
Zhang Sheng [1 ]
Zhang Yingyao [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
vacuum interrupter; X-radiation; power-frequency voltage; contact gap; voltage conditioning; CIRCUIT-BREAKERS;
D O I
10.1088/1009-0630/18/5/22
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
When subjected to high voltages between opened contacts, vacuum interrupters may emit X-rays. In order to ensure that these are of an acceptable level, vacuum interrupters should comply with the limits for X-ray emission and the test procedures to be carried out to verify this based on relevant standards and specifications. In this paper, a comprehensive experimental study has been performed for 126 kV vacuum interrupters used in a transmission system to understand the X-radiation level and its influence by three main parameters, namely applied power-frequency voltage, contact gap and power-frequency voltage conditioning. The radiation instrument is an FJ347 radiometer and the X-radiation dose was measured at the power-frequency test voltage. These tests demonstrated that the X-radiation emission level for a 126 kV vacuum interrupter did not exceed the following: 5 mu Sv per hour at a rated voltage of 126 kV and 150 mu Sv per hour at a power-frequency voltage of 230 kV at 1 m distance. The X-radiation dose increased with the applied power-frequency voltage increasing and decreased with the contact gap increasing. The X-radiation dose for 126 kV vacuum interrupters decreased by 57% after the conditioning procedure with a certain power-frequency voltage. During the conditioning procedure, the average value of the X-radiation dose was 4.49 mSv, which means if a professional conditions 180 interrupters per year, it will be safe at the 6.4 m distance.
引用
收藏
页码:577 / 582
页数:6
相关论文
共 13 条
  • [1] [Anonymous], 2007, 622711 IEC
  • [2] [Anonymous], 2007, VACUUM INTERRUPTER T
  • [3] *ANSI, 1989, C3785 ANSI
  • [4] Boxman R.L., 1995, Handbook of Vacuum Arc Science and Technology
  • [5] Chinese Standards, 2002, GB188712002 CHIN STA
  • [6] Garzon RubenD., 2002, HIGH VOLTAGE CIRCUIT
  • [7] Greenwood A., 1994, VACUUM SWITCHGEAR
  • [8] History of vacuum circuit breakers and recent developments in Japan
    Homma, M
    Sakaki, M
    Kaneko, E
    Yanabu, S
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (01) : 85 - 92
  • [9] Li Wei, 2007, High Voltage Engineering, V33, P101
  • [10] Development of high-voltage vacuum circuit breakers in China
    Liu, Zhiyuan
    Wang, Jimei
    Xiu, Shixin
    Wang, Zhongyi
    Yuan, Shun
    Jin, Li
    Zhou, Heming
    Yang, Ren
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2007, 35 (04) : 856 - 865