Development of a nodal effective load model considering transmission system element unavailabilities

被引:16
作者
Choi, J [1 ]
Billinton, R
Futuhi-Firuzabed, M
机构
[1] Gyeongsang Natl Univ, Dept Elect Engn, Chinju, GN, South Korea
[2] Univ Saskatchewan, Dept Elect Engn, Saskatoon, SK S7N 5A9, Canada
[3] Sharif Univ Technol, Dept Elect Engn, Tehran, Iran
关键词
D O I
10.1049/ip-gtd:20041132
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper illustrates an extended effective load model including the capacities and uncertainties of generators and transmission lines. The conventional effective load model only considers the uncertainties of generators. An extended ELDC (effective load duration curve) based on the effective load model is proposed in the paper. The proposed nodal ELDC is able to supply information on nodal indices for probabilistic production cost simulation and reliability evaluation at the load points in a power system. It is expected that the effective load model presented in the paper will prove useful in many problems dealing with nodal and decentralised operation and control of electric power systems in the competitive electricity market environment. The proposed ELDC will extend the application areas of nodal probabilistic production cost simulation, outage cost assessment and reliability evaluation etc. at load points. The characteristics and effectiveness of this new effective load model are illustrated using case studies of test systems.
引用
收藏
页码:79 / 89
页数:11
相关论文
共 24 条
[1]  
[Anonymous], 1998, Power systems restructuring: engineering and economics
[2]  
[Anonymous], ELECT ENERGY GENERAT
[3]   Enhanced adequacy equivalent for composite power system reliability evaluation [J].
Billinton, R ;
Zhang, W .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (05) :420-426
[4]  
Billinton R, 1995, IEEE WESCANEX '95 - COMMUNICATIONS, POWER, AND COMPUTING, CONFERENCE PROCEEDINGS, VOLS 1 AND 2, P145, DOI 10.1109/WESCAN.1995.493961
[5]   COMPOSITE SYSTEM RELIABILITY EVALUATION [J].
BILLINTON, R .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (04) :276-+
[6]   A SECURITY BASED APPROACH TO COMPOSITE POWER-SYSTEM RELIABILITY EVALUATION [J].
BILLINTON, R ;
KHAN, E ;
ENDRENYI, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :65-72
[7]  
Billinton R., 1984, RELIABILITY EVALUATI
[8]  
Billinton R., 1994, Reliability assessment of electrical power systems using Monte Carlo methods
[9]   POWER ARRIVAL EVALUATION OF BULK SYSTEM INCLUDING NETWORK CONSTRAINTS BASED ON LINEAR-PROGRAMMING APPROACH [J].
CHEN, LN ;
SUWA, H ;
TOYODA, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (01) :37-42
[10]  
CHOI J, 1999, LESCOPE 99, P189