摘要
The design and optimization of ground source heat pump systems require the ability to accurately reproduce the dynamic thermal behavior of the system on a short-term basis, specially in a system control perspective. In this context, modeling borehole heat exchangers (BHEs) is one of the most relevant and difficult tasks. Developing a model that is able to accurately reproduce the instantaneous response of a BHE while keeping a good agreement on a long-term basis is not straightforward. Thus, decoupling the short-term and long-term behavior will ease the design of a fast short-term focused model. This work presents a short-term BHE dynamic model, called Borehole-to-Ground (B2G), which is based on the thermal network approach, combined with a vertical discretization of the borehole. The proposed model has been validated against experimental data from a real borehole located in Stockholm, Sweden. Validation results prove the ability of the model to reproduce the short-term behavior of the borehole with an accurate prediction of the outlet fluid temperature, as well as the internal temperature profile along the U-tube. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:210 / 223
页数:14
相关论文
共 47 条
[1]  
Acuna J., 2009, P EFFST 2009 11 INT
[2]  
Acuna J, 2008, ZUR IEA HEAT PUMP C
[3]  
ACUNA J, 2013, THESIS KTH
[4]   Energy analysis of a solar-ground source heat pump system with vertical closed-loop for heating applications [J].
Bakirci, Kadir ;
Ozyurt, Omer ;
Comakli, Kemal ;
Comakli, Omer .
ENERGY, 2011, 36 (05) :3224-3232
[5]   Transient 3D analysis of borehole heat exchanger modeling [J].
Bauer, D. ;
Heidemann, W. ;
Diersch, H. -J. G. .
GEOTHERMICS, 2011, 40 (04) :250-260
[6]   Thermal resistance and capacity models for borehole heat exchangers [J].
Bauer, D. ;
Heidemann, W. ;
Mueller-Steinhagen, H. ;
Diersch, H. -J. G. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2011, 35 (04) :312-320
[7]   Investigations on the influence of aquifers on the ground temperature in ground-source heat pump operation [J].
Capozza, Antonio ;
De Carli, Michele ;
Zarrella, Angelo .
APPLIED ENERGY, 2013, 107 :350-363
[8]  
Carslaw H.S., 2000, Conduction of Heat in Solids, VSecond
[9]   A quasi-steady state mathematical model of an integrated ground source heat pump for building space control [J].
Corberan, J. M. ;
Finn, D. P. ;
Montagud, C. M. ;
Murphy, F. T. ;
Edwards, K. C. .
ENERGY AND BUILDINGS, 2011, 43 (01) :82-92
[10]  
De Rosa M, 2014, 32 UIT HEAT TRANSF C