Single Line to Ground Fault Detection in a Non-Effectively Grounded Distribution Network

被引:81
作者
Wang, Xiaowei [1 ,2 ]
Gao, Jie [3 ]
Wei, Xiangxiang [4 ]
Zeng, Zhihui [2 ]
Wei, Yanfang [2 ]
Kheshti, Mostafa [5 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] Henan Polytech Univ, Sch Elect Engn & Automat, Jiaozuo 454000, Peoples R China
[3] State Grid Zhejiang Elect Power Co Ltd, Wenzhou Power Supply Co, Wenzhou 325000, Peoples R China
[4] Tech Univ Berlin, D-10623 Berlin, Germany
[5] Shandong Univ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Shandong, Peoples R China
基金
中国国家自然科学基金;
关键词
Faulted feeder detection; instantaneous amplitude; instantaneous phase; instantaneous energy; polarity; PHASE; FEEDER; TIME; SPECTRUM;
D O I
10.1109/TPWRD.2018.2873017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In the event of a single line to ground (SLG) fault in a non-effectively grounded distribution network, the faulted current is weak (only a few amperes or less) and the existing devices cannot accurately judge the faulted feeder. In this paper, we proposed algorithms that combine complete ensemble empirical mode decomposition with adaptive noise (CEEMDAN) and Hilbert transform to construct a multi-criteria comprehensive voting method. First, CEEMDAN algorithm is used to decompose the zero-sequence current to obtain the IMF1 (the first intrinsic mode function) component and the Hilbert transform is used to calculate the instantaneous amplitude and instantaneous phase. Then, according to the three largest instantaneous amplitudes information, we constructed the characteristic instantaneous phase, characteristic instantaneous energy relative entropy and characteristic instantaneous zero sequence current polarity criteria from the phase, energy and polarity, respectively. Finally, we proposed a comprehensive voting method, which is specifically shown as follows: when two or more criteria show that one feeder or the bus has an SLG fault, it is voted that the feeder or the bus has an SLG fault. In contrast, if the judgment results of the three criteria are inconsistent, then we would return to recalculation and then vote. Compared with existing method, simulation tests and field experiments show that the method proposed in this paper has higher accuracy and a faster calculation speed.
引用
收藏
页码:3173 / 3186
页数:14
相关论文
共 32 条
[1]  
[Anonymous], 2015, P IEEE WORKSH LOC ME
[2]   A Decentralized Fault Detection Technique for Detecting Single Phase to Ground Faults in Power Distribution Systems With Resonant Grounding [J].
Barik, Md. Abdul ;
Gargoom, Ameen ;
Mahmud, Md. Apel ;
Haque, Md. Enamul ;
Al-Khalidi, Hassan ;
Oo, Amanullah Maung Than .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) :2462-2473
[3]  
Barisione M, 2017, PALGRAVE ST EUR POL, P1, DOI 10.1057/978-1-137-59890-5_1
[4]   Integrated Use of Time-Frequency Wavelet Decompositions for Fault Location in Distribution Networks: Theory and Experimental Validation [J].
Borghetti, A. ;
Bosetti, M. ;
Nucci, C. A. ;
Paolone, M. ;
Abur, A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :3139-3146
[5]  
Carpenter M., 2004, P 31 ANN W PROT REL, P1
[6]   PRONYS METHOD - AN EFFICIENT TOOL FOR THE ANALYSIS OF EARTH FAULT CURRENTS IN PETERSEN-COIL-PROTECTED NETWORKS [J].
CHAARI, O ;
BASTARD, P ;
MEUNIER, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) :1234-1241
[7]   Hilbert-Transform-Based Transient/Intermittent Earth Fault Detection in Noneffectively Grounded Distribution Systems [J].
Cui, Tao ;
Dong, Xinzhou ;
Bo, Zhiqian ;
Juszczyk, Andrzej .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :143-151
[8]   Single-ended travelling wave protection algorithm based on full waveform in the time and frequency domains [J].
Deng, Feng ;
Li, Xinran ;
Zeng, Xiangjun .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (15) :3680-3691
[9]   Identifying single-phase-to-ground fault feeder in neutral noneffectively grounded distribution system using wavelet transform [J].
Dong, Xinzhou ;
Shi, Shenxing .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :1829-1837
[10]   Prony-based optimal bayes fault classification of overcurrent protection [J].
Faiz, Jawad ;
Lotfi-fard, Saeed ;
Shahri, Saied Haidarian .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1326-1334