Ground resistance measurement with alternative fall-of-potential method

被引:17
作者
Korasli, C [1 ]
机构
[1] Univ Bahrain, Dept Elect & Elect Engn, Isa Town 32038, Bahrain
关键词
fall-of-potential; ground electrode systems; ground resistance measurement; grounding;
D O I
10.1109/TPWRD.2004.833922
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An. alternative fall-of-potential method is presented to measure on-line and in situ resistance of ground electrode systems in low-voltage distribution networks. It provides simultaneous resistance measurements of both equivalent ground electrode system of a substation and ground electrode of a premise. The method does not require usage of any auxiliary electrode, but employs two existing ground electrodes in the distribution network. The method has the advantage that it uses moderately high currents than the classical fall-of-potential method, and results are independent of test electrode positions. The method is especially useful in urbanized districts where it is difficult to apply the classical fall-of-potential method. Also, a capacitive potential probe was successfully tested in place of the current electrode used in the fall-of-potential method.
引用
收藏
页码:1657 / 1661
页数:5
相关论文
共 4 条
[1]  
*IEEE, 1983, IEEE GUID MEAS GROUN
[2]   Extended analysis of ground impedance measurement using the fall-of-potential method [J].
Ma, JX ;
Dawalibi, FP .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :881-885
[3]   Influence of inductive coupling between leads on ground impedance measurements using the Fall-of-Potential method [J].
Ma, JX ;
Dawalibi, FP .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :739-743
[4]   Backtracking tactics in the backtrack method for SAT [J].
Wang, J .
MATHEMATICAL AND COMPUTER MODELLING, 1998, 28 (02) :1-12