Effect of TCPS on oscillations in tie-power and area frequencies in an interconnected hydrothermal power system

被引:40
作者
Abraham, R. J. [1 ]
Das, D. [1 ]
Patra, A. [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, Kharagpur 721302, W Bengal, India
关键词
D O I
10.1049/iet-gtd:20060361
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The analysis of automatic generation control of a two-area interconnected hydrothermal power system considering a thyristor-controlled phase shifter (TCPS) in series with the tie-line is presented. It is possible to damp the system frequency and tie-power oscillations by controlling the phase angle of TCPS. A control strategy using TCPS is proposed to provide active control of system frequency. Gain settings of the integral controllers with and without considering TCPS are optimised using integral squared error technique following a step load disturbance in each of the areas by minimising a quadratic performance index. Analysis reveals that a TCPS is quite capable of suppressing the frequency and tie-power oscillations effectively under the occurrence of sudden load changes in any of the areas when compared with that obtained without TCPS.
引用
收藏
页码:632 / 639
页数:8
相关论文
共 22 条
[1]  
[Anonymous], 1973, IEEE T POWER AP SYST, VPA92, P1904, DOI 10.1109/TPAS.1973.293570
[2]   MODELING AND TESTING OF VALLEY STEAM PLANT SUPPLEMENTAL EXCITATION CONTROL-SYSTEM [J].
HAYES, DR ;
CRAYTHORN, GE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (02) :464-470
[3]   CONTROL ALGORITHM FOR A STATIC PHASE-SHIFTING TRANSFORMER TO ENHANCE TRANSIENT AND DYNAMIC STABILITY OF LARGE POWER-SYSTEMS [J].
BAKER, R ;
GUTH, G ;
EGLI, W ;
EGLIN, P .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (09) :3532-3542
[4]   REGULATION ERROR IN LOAD FREQUENCY CONTROL [J].
BOSE, A ;
ATIYYAH, I .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (02) :650-657
[5]   TECHNIQUES FOR IMPROVING CONTROL OF BULK POWER TRANSFERS ON INTERCONNECTED SYSTEMS [J].
COHN, N .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (06) :2409-&
[6]   AUTOMATIC-GENERATION CONTROL OF A HYDROTHERMAL SYSTEM WITH NEW AREA CONTROL ERROR CONSIDERING GENERATION RATE CONSTRAINT [J].
DAS, D ;
NANDA, J ;
KOTHARI, ML ;
KOTHARI, DP .
ELECTRIC MACHINES AND POWER SYSTEMS, 1990, 18 (06) :461-471
[7]   HYDRAULIC-TURBINE AND TURBINE CONTROL-MODELS FOR SYSTEM DYNAMIC STUDIES [J].
DEMELLO, FP ;
KOESSLER, RJ ;
AGEE, J ;
ANDERSON, PM ;
DOUDNA, JH ;
FISH, JH ;
HAMM, PAL ;
KUNDUR, P ;
LEE, DC ;
ROGERS, GJ ;
TAYLOR, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :167-179
[8]   OPTIMUM MEGAWATT-FREQUENCY CONTROL OF MULTIAREA ELECTRIC ENERGY SYSTEMS [J].
ELGERD, OI ;
FOSHA, CE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (04) :556-&
[9]   Transformed automatic generation control [J].
Green, RK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (04) :1799-1804
[10]  
Hingorani Narain G., 2000, UNDERSTANDING FACTS