phasor measurement; power generation protection; power utilisation; power generation dispatch; power generation faults; power system restoration; power distribution faults; power distribution protection; data acquisition; loss-of-main protection system; phasor measurement unit technology; experimentally assessed threshold setting; embedded generator disconnection; utility grid; utility dispatched generation; fault restoration; personnel safety; plant protection; out-of-synchronism reclosure; nuisance devices tripping; current islanding detection method; PMU technology; distribution network application; zero non-detection zone; Ireland power system; Great Britain power system; ISLANDING DETECTION; CURRENT INJECTION; SYNCHRONIZATION; ALTERNATOR; GENERATOR;
D O I
10.1049/iet-gtd.2014.0106
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Loss-of-mains protection is an important component of the protection systems of embedded generation. The role of loss-of-mains is to disconnect the embedded generator from the utility grid in the event that connection to utility dispatched generation is lost. This is necessary for a number of reasons, including the safety of personnel during fault restoration and the protection of plant against out-of-synchronism reclosure to the mains supply. The incumbent methods of loss-of-mains protection were designed when the installed capacity of embedded generation was low, and known problems with nuisance tripping of the devices were considered acceptable because of the insignificant consequence to system operation. With the dramatic increase in the installed capacity of embedded generation over the last decade, the limitations of current islanding detection methods are no longer acceptable. This study describes a new method of loss-of-mains protection based on phasor measurement unit (PMU) technology, specifically using a low cost PMU device of the authors' design which has been developed for distribution network applications. The proposed method addresses the limitations of the incumbent methods, providing a solution that is free of nuisance tripping and has a zero non-detection zone. This system has been tested experimentally and is shown to be practical, feasible and effective. Threshold settings for the new method are recommended based on data acquired from both the Great Britain and Ireland power systems.
引用
收藏
页码:146 / 153
页数:8
相关论文
共 9 条
[1]   Current transients in the small salient-pole alternator during sudden short-circuit and synchronisation events [J].
Best, R. J. ;
Morrow, D. J. ;
Crossley, P. A. .
IET ELECTRIC POWER APPLICATIONS, 2010, 4 (09) :687-700
[2]   Effect of loading, voltage difference and phase angle on the synchronisation of a small alternator [J].
Best, R. J. ;
Morrow, D. J. ;
Crossley, P. A. .
IET ELECTRIC POWER APPLICATIONS, 2009, 3 (06) :531-542
[3]   Synchronous islanded operation of a diesel generator [J].
Best, Robert J. ;
Morrow, D. John ;
McGowan, David J. ;
Crossley, Peter A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (04) :2170-2176
[4]   Synchrophasor Broadcast Over Internet Protocol for Distributed Generator Synchronization [J].
Best, Robert J. ;
Morrow, D. John ;
Laverty, David M. ;
Crossley, Peter A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2835-2841
[5]   Current injection for active islanding detection of electronically-interfaced distributed resources [J].
Hernandez-Gonzalez, Guillermo ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1698-1705
[6]   Negative-sequence current injection for fast islanding detection of a distributed resource unit [J].
Karimi, Houshang ;
Yazdani, Amirnaser ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (01) :298-307
[7]   An Islanding Detection Method for a Grid-Connected System Based on the Goertzel Algorithm [J].
Kim, Jae-Hyung ;
Kim, Jun-Gu ;
Ji, Young-Hyok ;
Jung, Yong-Chae ;
Won, Chung-Yuen .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (04) :1049-1055
[8]   The OpenPMU Platform for Open-Source Phasor Measurements [J].
Laverty, David M. ;
Best, Robert J. ;
Brogan, Paul ;
Al Khatib, Iyad ;
Vanfretti, Luigi ;
Morrow, D. John .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2013, 62 (04) :701-709
[9]  
SEL Inc, 2010, CAS STUD APPL NOT