Study of Physicochemical and Bacteriological Quality of Treated Wastewater by the New Aourir Plant (Southwestern of Morocco) Using Activated Sludge Technology in a Semi-Arid Region

被引:12
作者
Haji, Sara [1 ]
Alla, Aicha Ait [1 ]
Noureddine, Slimani [1 ]
Ben Haddad, Mohamed [1 ]
Moukrim, Abdellatif [2 ]
机构
[1] Ibn Zohr Univ, Fac Sci, Lab Aquat Syst Marine & Continental Ecosyst, Agadir, Morocco
[2] Abdelamalek Essadi Univ, Fac Sci, Tetouan, Morocco
来源
JOURNAL OF ECOLOGICAL ENGINEERING | 2021年 / 22卷 / 06期
关键词
wastewater; Morocco; physicochemical parameters; activated sludge; Aourir; bacteriological param-eters; treatment plants; REUSE; FILTRATION; RESISTANCE; BACTERIA; SEWAGE; LAGOON; SOIL;
D O I
10.12911/22998993/137360
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In order to use the purified wastewater for the irrigation of a golf course in the Taghazout area (Southwestern of Morocco), this study was conducted to evaluate the physicochemical and bacteriological quality of the treated wastewater in the new Aourir plant (Activated Sludge technology). In order to achieve these objectives, three types of water were analyzed: raw water (RW), biologically treated water (BTW) and water treated by ultraviolet radiation (UV-TW). The physicochemical parameters analyzed were Temperature, pH, Electrical Conductivity (EC), Dissolved Oxygen (DO), Chemical Oxygen Demand (COD), five-day Biological Oxygen Demand (BOD5), Total Suspended Solids (SS), Nitrate (NO3), and Orthophosphates (PO4). Otherwise, the analyzed biological parameters are Total Coliforms (TC), Fecal Coliforms (FC), Escherichia coli (E. coli), and Fecal Streptococci (FS). The physicochemical parameters showed that temperature is always lower than 30 degrees C, the pH is close to neutrality and a strong fluctuation of the high electrical conductivity (2700 mu S/cm) occurs in UV-TW. At all stages of wastewater treatment, COD, BOD5, SS, NO3 and PO4 were below the limit values recommended by Moroccan standards. The bacteriological results showed a high level of bacterial contamination in RW and BTW, but in UV-TW the loads did not exceed 3 log10. The average loads of TC, FC, E. coli and FC in UV-TW were 2.13, 1.67, 1.77, and 2 (log10 CFU/100ml) respectively. Activated sludge treatment combined with UV has demonstrated sufficient quality to reuse treated water in irrigation; however, the UV treatment requires control to avoid any effect on the microbiological and physicochemical quality of green spaces and groundwater.
引用
收藏
页码:83 / 98
页数:16
相关论文
共 55 条
[31]   Sand filtration of wastewater for tertiary treatment and water reuse [J].
Hamoda, MF ;
Al-Ghusain, I ;
Al-Mutairi, NZ .
DESALINATION, 2004, 164 (03) :203-211
[32]  
Hassoune E.M., 2006, Bull. Linstitut Sci. Rabat, V28, P61
[33]  
Joel C, 2018, MICROBIOL RES-ITALY, V9, P14
[34]   Occurrence and behavior of pesticides in wastewater treatment plants and their environmental impact [J].
Koeck-Schulmeyer, Marianne ;
Villagrasa, Marta ;
Lopez de Alda, Miren ;
Cespedes-Sanchez, Raquel ;
Ventura, Francesc ;
Barcelo, Damia .
SCIENCE OF THE TOTAL ENVIRONMENT, 2013, 458 :466-476
[35]  
Lazarova V, 1998, WATER SCI TECHNOL, V38, P109, DOI 10.1016/S0273-1223(98)00810-5
[36]  
Makhoukh M, 2011, LARHYSS J, V9, P21
[37]   Seasonal variation in bacterial flora of the wastewater and soil in the vicinity of industrial area [J].
Malik, A ;
Ahmad, M .
ENVIRONMENTAL MONITORING AND ASSESSMENT, 2002, 73 (03) :263-273
[38]  
Mandi L., 2013, SUSTAINABLE SANITATI, V1, P9
[39]  
Merghem KA, 2016, MOROC J CHEM, V4, P731
[40]   RESISTANCE PATTERNS OF ESCHERICHIA-COLI STRAINS ISOLATED FROM DOMESTIC SEWAGE BEFORE AND AFTER TREATMENT IN BOTH AEROBIC LAGOON AND ACTIVATED-SLUDGE [J].
MEZRIOUI, N ;
BALEUX, B .
WATER RESEARCH, 1994, 28 (11) :2399-2406