Energy Management System for Grid-Connected Nanogrid during COVID-19

被引:3
作者
Jamal, Saif [1 ]
Pasupuleti, Jagadeesh [2 ]
Rahmat, Nur Azzammudin [3 ]
Tan, Nadia M. L. [4 ]
机构
[1] Univ Tenaga Nas, Coll Engn, Dept Elect & Elect Engn, Kajang 43000, Selangor, Malaysia
[2] Univ Tenaga Nas, Inst Sustainable Energy, Kajang 43000, Selangor, Malaysia
[3] Univ Tenaga Nas, Dept Elect Power Engn, Kajang 43000, Selangor, Malaysia
[4] Univ Nottingham Ningbo China, Key Lab More Elect Aircraft Technol Zhejiang Prov, Ningbo 315100, Zhejiang, Peoples R China
关键词
nanogrid; energy management system; Stateflow; photovoltaic; energy storage system; DUAL-ACTIVE-BRIDGE; OPTIMIZATION; DESIGN;
D O I
10.3390/en15207689
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An effective energy management system (EMS) was designed based on the Stateflow (SF) approach for a grid-connected nanogrid (NG) composed of a photovoltaic (PV) array with a battery bank and supercapacitor (SC) energy storage system (ESS). The PV energy system, battery bank and SC (ESS), dual active bridge DC/DC converters, DC/AC inverters, control algorithms, and controllers were developed to test the operation of the NG. The average and high-frequency power components are separated using frequency division of the ESS power utilizing a low-pass filter; the average power is absorbed by the battery bank, while the high-frequency power is absorbed by the SC. The aim of this paper is to design an EMS to manage the energy of a grid-connected NG system considering the availability of the PV array, ESS, and demand requirements. Different scenarios of operation were tested to check the EMS behaviour during the day with a random demand profile, including: (1) a PV array with the grid supplying the load without an EMS; (2) a PV array, batteries, and the grid supplying the load with an EMS; (3) a PV array, batteries, an SC, and the grid supplying the load with an EMS; (4) a PV array, batteries, an SC, and the grid supplying the load with an EMS, with load profile reduction by 20% due to COVID-19. As per the simulation results, the proposed EMS enables the flow of power in the NG system and demonstrates the impact on the ESS by minimising carbon emissions via a reduction in grid consumption. Furthermore, the SF method is regarded as a helpful alternative to popular design approaches employing conventional software tools.
引用
收藏
页数:20
相关论文
共 28 条
  • [21] Generalized Average Modeling of Dual Active Bridge DC-DC Converter
    Qin, Hengsi
    Kimball, Jonathan W.
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (04) : 2078 - 2084
  • [22] Bidirectional Power Sharing for DC Microgrid Enabled by Dual Active Bridge DC-DC Converter
    Rios, Sara J.
    Pagano, Daniel J.
    Lucas, Kevin E.
    [J]. ENERGIES, 2021, 14 (02)
  • [23] Different Purpose Design Strategies and Techniques to Improve the Performance of a Dual Active Bridge With Phase-Shift Control
    Rodriguez, Alberto
    Vazquez, Aitor
    Lamar, Diego G.
    Hernando, Marta M.
    Sebastian, Javier
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (02) : 790 - 804
  • [24] Scheduling controller for microgrids energy management system using optimization algorithm in achieving cost saving and emission reduction
    Roslan, M. F.
    Hannan, M. A.
    Ker, Pin Jern
    Begum, R. A.
    Mahlia, T. M. Indra
    Dong, Z. Y.
    [J]. APPLIED ENERGY, 2021, 292
  • [25] Modeling and Advanced Control of Dual-Active-Bridge DC-DC Converters: A Review
    Shao, Shuai
    Chen, Linglin
    Shan, Zhenyu
    Gao, Fei
    Chen, Hui
    Sha, Deshang
    Dragicevic, Tomislav
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (02) : 1524 - 1547
  • [26] An Energy Management System for the Control of Battery Storage in a Grid-Connected Microgrid Using Mixed Integer Linear Programming
    Sigalo, Marvin Barivure
    Pillai, Ajit C.
    Das, Saptarshi
    Abusara, Mohammad
    [J]. ENERGIES, 2021, 14 (19)
  • [27] Young B, 2016, AUSTR UNIV POWER ENG
  • [28] Uncertainty models for stochastic optimization in renewable energy applications
    Zakaria, A.
    Ismail, Firas B.
    Lipu, M. S. Hossain
    Hannan, M. A.
    [J]. RENEWABLE ENERGY, 2020, 145 (145) : 1543 - 1571