A Minute Asymmetrical Current Injection Based Anti-islanding Method for Three-Phase Grid-Connected Photovoltaic Inverters

被引:5
作者
Sun, Xiang-Dong [1 ]
Matsui, Mikihiko [1 ]
Yu, Byung-Gyu [2 ]
Koh, Kang-Hoon [3 ]
机构
[1] Tokyo Polytech Univ, Dept Syst Elect & Informat Technol, Atsugi, Kanagawa 2430297, Japan
[2] Korea Inst Energy Res, Dept Elect Engn, Taejon 305343, South Korea
[3] Kyungnam Univ, Photovolta Res Grp, Masan 631701, South Korea
关键词
islanding detection; asymmetrical current injection; non-detection zone; zero-crossing; OPERATION;
D O I
10.1002/tee.20608
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An active anti-islanding protection method based on the current control for a three-phase grid-connected photovoltaic inverter is proposed in this paper. The current of phase-a is synchronous with the corresponding phase voltage at the point of common coupling in its positive half cycle, and a zero-current zone is inserted at the end of the cycle in a negative half cycle. As for phase-c, the zero-current zone is inserted in the positive half cycle of the current, and the current in a negative half cycle of phase-c is in phase with the corresponding phase voltage. Therefore, the currents of phase-a and phase-c in one cycle become slightly asymmetrical. Before the islanding takes place, the positive and negative half cycles of three-phase voltages are symmetrical due to the operation of the grid voltage. While islanding takes place, a time difference between the positive and negative half cycles of the voltages of phase-a and phase-c will be generated and the islanding is detected in accordance with the successive cycles fulfilling the conditions of islanding identification. In order to measure zero-crossings of the voltages accurately, an finite impulse response filter is used to smooth out the voltage harmonics and noises. Simulations and experiments for three-phase three-wire power systems have been carried out. The results verify that the proposed method can detect the islanding for a parallel RLC load or induction motors when the voltage frequency is within the range of the non-detection zone. It is seen from the analysis of the detecting principle that there is no influence of temporal voltage frequency fluctuation on the proposed method even if a large load connected to a weak power system frequently starts up or stops. (C) 2010 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
引用
收藏
页码:65 / 72
页数:8
相关论文
共 11 条
[1]  
CHOI J, 2005, EPE 2005 DRESD, P1
[2]   Design and operation of grid-connected photovoltaic system with power-factor control and active islanding detection [J].
Huang, SJ ;
Pai, FS .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2001, 148 (03) :243-250
[3]   Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters [J].
Hung, GK ;
Chang, CC ;
Chen, CL .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2003, 18 (01) :169-173
[4]   Development of a robust anti-islanding algorithm for utility interconnection of distributed fuel cell powered generation [J].
Jeraputra, C ;
Enjeti, PN .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1163-1170
[5]  
KITAMURA A, 1994, IEEE PHOT SPEC CONF, P759, DOI 10.1109/WCPEC.1994.520070
[6]  
KOBAYASHI H, 1991, IEEE PHOT SPEC CONF, P695, DOI 10.1109/PVSC.1991.169299
[7]  
*POW INC, 2003, PSIM US GUID VERS 6
[8]  
REY AB, 2004, POWER ELECT MACHINES, V2, P609
[9]   Predicting islanding operation of grid connected PV inverters [J].
Smith, GA ;
Onions, PA ;
Infield, DG .
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 2000, 147 (01) :1-6
[10]  
Tunlasakun K, 2004, TENCON IEEE REGION, pD175