Adaptability of a temperature and humidity independent control air- conditioning system in green office buildings

被引:25
作者
Niu, Runping [1 ]
Fan, Yingying [1 ]
Geng, Lizhi [1 ]
机构
[1] Beijing Univ Civil Engn & Architecture, Sch Environm & Energy Engn, Beijing 100044, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2021年 / 42卷
基金
中国国家自然科学基金; 国家重点研发计划;
关键词
THIC; Green office buildings; Humidity hours; Building energy simulation; Dynamic recovery period; ENERGY-CONSUMPTION; PERFORMANCE;
D O I
10.1016/j.jobe.2021.102432
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In order to reduce the energy consumption and improve the economy of air conditioning system, theoretical analysis and energy consumption simulation are used in this paper to explore the adaptability of temperature and humidity independent control (THIC) air-conditioning system in green office buildings. On the basis of the air moisture content and working hours of staf f in green office buildings, China was divided into four humidity-hour zones, and several typical cities were selected in each zone for the same building to carry out the analyses of energy consumption simulation and dynamic recovery period of different THIC air conditioning systems in office buildings. The results indicated that in Urumqi, as the representative city of humidity-hour zone I, green office buildings do not suit THIC system; THIC air conditioning system shows obvious advantages over traditional air conditioning in terms of energy saving and economy, and the energy saving rate of the most suitable THIC air conditioning system in Harbin, Beijing and Haikou, as the representative city of humidity-hour zone II, zone III and zone IV, reached 28 .0 4% , 24 .6 4% , and 24 .4 2% respectively. Based on the number of humidity-hour, the most suitable THIC air conditioning systems for typical cities in different zone were raised, and a reference for the use of THIC air conditioning system in green office buildings was provided in this paper.
引用
收藏
页数:9
相关论文
共 26 条
  • [1] Performance assessment of hybrid chiller systems for combined cooling, heating and power production
    Ahn, Hyeunguk
    Rim, Donghyun
    Freihaut, James D.
    [J]. APPLIED ENERGY, 2018, 225 : 501 - 512
  • [2] Ashrae, 2013, STANDARD 55 THERMAL
  • [3] Hybrid adsorption cooling systems-An overview
    Askalany, Ahmed A.
    Saha, Bidyut B.
    Kariya, Keishi
    Ismail, Ibrahim M.
    Salem, Mahmoud
    Ali, Ahmed H. H.
    Morsy, Mahmoud G.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (08) : 5787 - 5801
  • [4] On the performances of a hybrid air-conditioning system in different climatic conditions
    Bergero, Stefano
    Chiari, Anna
    [J]. ENERGY, 2011, 36 (08) : 5261 - 5273
  • [5] Ca o L. H., 2016, THESIS HEBEI U ENG H
  • [6] Ch en Y. Z., 2014, ICCREM, V145, P364, DOI [10.1061/9780784413777.043, DOI 10.1061/9780784413777.043]
  • [7] Applicability and energy efficiency of temperature and humidity independent control systems based on dual cooling sources
    Chen, Tingting
    Yin, Yonggao
    Zhang, Xiaosong
    [J]. ENERGY AND BUILDINGS, 2016, 121 : 22 - 31
  • [8] An experimental study on a novel direct expansion based temperature and humidity independent control air conditioning system
    Chen, Wenjing
    Fang, Guanyu
    Wang, Caixia
    Weng, Wenbing
    Chan, Ming-yin
    Deng, Shiming
    Liu, Xuefeng
    Yan, Huaxia
    [J]. INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS, 2019, 158 : 2237 - 2243
  • [9] Daokai Wu, 2014, Advanced Materials Research, V953-954, P1561, DOI 10.4028/www.scientific.net/AMR.953-954.1561
  • [10] Ding Y. F., 2001, FLUID MACH, V29, P25, DOI [10.3969/j.issn.1005-0329.2001.03.007, DOI 10.3969/J.ISSN.1005-0329.2001.03.007]