Investigation on thermal performance of the wall-mounted attached ventilation for night cooling under hot summer conditions

被引:16
作者
Ji, Wenhui [1 ,2 ]
Luo, Qing [1 ,2 ]
Zhang, Zili [3 ]
Wang, Houhua [1 ,2 ]
Du, Tao [1 ,2 ]
Heiselberg, Per Kvols [4 ]
机构
[1] Chongqing Univ, Dept Urban Construct & Environm Engn, Chongqing 400045, Peoples R China
[2] Minist Educ, Key Lab Gorges Reservoir Reg Ecoenvironm 3, Chongqing 400045, Peoples R China
[3] Aarhus Univ, Dept Engn, DK-8000 Aarhus, Denmark
[4] Aalborg Univ, Dept Civil Engn, DK-9220 Aalborg, Denmark
基金
中国国家自然科学基金;
关键词
Night ventilation; Wall-attached jet; Convective heat transfer; Heat removal; Temperature efficiency; IMPINGING JET VENTILATION; AIR CURTAIN VENTILATION; CONFLUENT JETS; DISPLACEMENT VENTILATION; COMFORT PARAMETERS; BUILDINGS; ENERGY; SYSTEMS; OFFICE; FLOW;
D O I
10.1016/j.buildenv.2018.10.002
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In Hot Summer and Cold Winter Climate Zone, the cooling potential of natural/passive night ventilation is limited during summer due to the insignificant difference between the outdoor and indoor temperatures. Therefore, a novel mechanical ventilation strategy, the wall-mounted attached ventilation (WAV) system, is proposed in the present paper to improve ventilation efficiency of night cooling. The idea is that WAV can produce a downward airflow over the internal wall surface that is somewhat similar to a sidewall jet, so as to achieve enhanced heat transfer in the room. This paper starts with a series of experiments in a test chamber, and continues with thermal analysis of the heat transfer characteristics and heat removal performance of WAV. The performance of night ventilation with WAV is further evaluated in terms of ventilation efficiency index and energy performance index. It is shown that the overall average value of the convective heat transfer coefficient at the internal wall surface with WAV is 10.79 W M-2 degrees C-1. With WAV, the amount of heat removed from the ventilated wall is about five times that in the natural night ventilation case, and the total amount of heat removed from the whole chamber is twice as much. The average value of the surface cooling effectiveness of WAV is 1.48, and the overall coefficient of performance (COP) of WAV turns out to be 26.8. As a night ventilation strategy, WAV is capable to achieve good cooling performance under hot summer conditions.
引用
收藏
页码:268 / 279
页数:12
相关论文
共 52 条
[11]   Investigation on the flow and thermal behavior of impinging jet ventilation systems in an office with different heat loads [J].
Chen, H. J. ;
Moshfegh, B. ;
Cehlin, M. .
BUILDING AND ENVIRONMENT, 2013, 59 :127-144
[12]   Numerical investigation of the flow behavior of an isothermal impinging jet in a room [J].
Chen, H. J. ;
Moshfegh, B. ;
Cehlin, M. .
BUILDING AND ENVIRONMENT, 2012, 49 :154-166
[13]   Numerical investigatipn of ventilation performance of different air supply devices in an office environment [J].
Chen, Huijuan ;
Janbakhsh, Setareh ;
Larsson, Ulf ;
Moshfegh, Bahram .
BUILDING AND ENVIRONMENT, 2015, 90 :37-50
[14]   Ventilation performance prediction for buildings: A method overview and recent applications [J].
Chen, Qingyan .
BUILDING AND ENVIRONMENT, 2009, 44 (04) :848-858
[15]  
China Planning Press, 2006, CODE THERMAL DESIGN
[16]   Theoretical and experimental investigation of wall confluent jets ventilation and comparison with wall displacement ventilation [J].
Cho, Youngjun ;
Awbi, Hazim B. ;
Karimipanah, Taghi .
BUILDING AND ENVIRONMENT, 2008, 43 (06) :1091-1100
[17]   Thermal mass activation by hollow core slab coupled with night ventilation to reduce summer cooling loads [J].
Corgnati, Stefano Paolo ;
Kindinis, Andrea .
BUILDING AND ENVIRONMENT, 2007, 42 (09) :3285-3297
[18]   Experimental evaluation of night ventilation phenomena [J].
Geros, V ;
Santamouris, M ;
Tsangrasoulis, A ;
Guarracino, G .
ENERGY AND BUILDINGS, 1999, 29 (02) :141-154
[19]   COMFORT, CLIMATE ANALYSIS AND BUILDING DESIGN GUIDELINES [J].
GIVONI, B .
ENERGY AND BUILDINGS, 1992, 18 (01) :11-23
[20]   Sensitivity analysis of predicted night cooling performance to internal convective heat transfer modelling [J].
Goethals, Kim ;
Breesch, Hilde ;
Janssens, Arnold .
ENERGY AND BUILDINGS, 2011, 43 (09) :2429-2441