The impact of electric overhead radiant heating on the indoor environment of historic churches

被引:52
作者
Samek, Lucyna [2 ]
De Maeyer-Worobiec, Anna [3 ]
Spolnik, Zoya [3 ]
Bencs, Laszlo [3 ]
Kontozova, Velichka [3 ]
Bratasz, Lukasz [1 ]
Kozlowski, Roman [1 ]
Van Grieken, Rene [3 ]
机构
[1] Polish Acad Sci, Inst Catalysis & Surface Chem, PL-30239 Krakow, Poland
[2] AGH Univ Sci & Technol, Dept Phys & Appl Comp Sci, PL-30059 Krakow, Poland
[3] Univ Antwerp, Dept Chem, B-2610 Antwerp, Belgium
关键词
heating of churches; radiant heaters; microclimate; air flows; suspended particulate matter; indoor and outdoor air; particle transport and deposition;
D O I
10.1016/j.culher.2007.03.006
中图分类号
K85 [文物考古];
学科分类号
0601 ;
摘要
The impact of electric overhead radiant heaters on the microclimate, air flows, transport and deposition of suspended particulate matter (SPM) was monitored between March 2004 and March 2005 in the historic churches of Saint Michael Archangel in Szalowa and Saint Catherine in Cracow (Poland). The measurements show that although irradiation at the floor level increases temperature and reduces relative humidity in the interior of the church, the effect out of the heated zone and for the surfaces sheltered from irradiation is very limited, i.e. their extent is comparable with natural fluctuations inherent to the local climate of the church. The radiant heaters proved to generate little convectional flow of the air. Therefore, the heating system was not found to increase the concentration of SPM indoors; in particular, no re-suspension of particles already present in the church was observed. This work has demonstrated that the overhead radiant heaters are capable of providing localised heat to the areas where people congregate without adversely affecting painted walls and the works of arts displayed in churches. Care, however, should be taken that sensitive works of art are not exposed to the direct infrared radiation. (C) 2007 Elsevier Masson SAS. All rights reserved.
引用
收藏
页码:361 / 369
页数:9
相关论文
共 11 条
[1]   Comparison of hot-air and low-radiant pew heating systems on the distribution and transport of gaseous air pollutants in the mountain church of Rocca Pietore from artwork conservation points of view [J].
Bencs, Laszlo ;
Spolnik, Zoya ;
Limpens-Neilen, Dionne ;
Schellen, Henk L. ;
Jutte, Bernhard A. H. G. ;
Van Grieken, Rene .
JOURNAL OF CULTURAL HERITAGE, 2007, 8 (03) :264-271
[2]  
Bordass W., 1996, Heating Your Church
[3]  
Bratasz L, 2005, STUD CONSERV, V50, P307
[4]  
Bratasz L., 2005, 14 TRIENN M HAG 12 1, P582
[5]  
CAMUFFO D, 2006, GUIDE ANAL PROS CONS
[6]  
Camuffo D., 1998, MICROCLIMATE CULTURA
[7]  
*CNR I SCI ATM CLI, FRIENDL HEAT BOTH CO
[8]  
Limpens-Neilen D., 2006, Bench Heating in Monumental Churches Thermal Performance of a Prototype (PhD Thesis). Eindhoven University of Technology
[9]  
Mecklenburg MF., 1998, PAINTED WOOD HIST CO, P464
[10]  
Padfield T., 1994, PREVENTIVE CONSERVAT, P94