Power system frequency estimation

被引:51
作者
Szafran, J [1 ]
Rebizant, W [1 ]
机构
[1] Wroclaw Univ Technol, Inst Elect Power Engn, PL-50370 Wroclaw, Poland
关键词
algorithm; power system frequency; signal components;
D O I
10.1049/ip-gtd:19982187
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new algorithm of power system frequency estimation is presented. The algorithm applies orthogonal signal components obtained with use of two orthogonal FIR filters. The essential property of the algorithm presented is its outstanding immunity to both signal orthogonal component magnitudes and FIR filter gains variations which ensures 1.5mHz accuracy of estimation over typical (+/-2Hz) range of measured frequency deviation. The results of the algorithm simulation tests using the EMTP software package are also included, It was confirmed that the algorithm dynamics are good enough to track power system frequency even under transient conditions.
引用
收藏
页码:578 / 582
页数:5
相关论文
共 5 条
[1]  
*LEUV CTR, 1987, EMT ATP REF MAN
[2]   Model system tests on a new numeric method of power system frequency measurement [J].
Moore, PJ ;
Carranza, RD ;
Johns, AT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :696-701
[3]   A NEW NUMERIC TECHNIQUE FOR HIGH-SPEED EVALUATION OF POWER-SYSTEM FREQUENCY [J].
MOORE, PJ ;
CARRANZA, RD ;
JOHNS, AT .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1994, 141 (05) :529-536
[4]  
MOORE PJ, 1993, IEE CONF PUBL, V368, P73
[5]  
Ungrad H., 1995, PROTECTION TECHNIQUE